RuggedCom RS969 manual IEEE 1613 Type Tests, IEC Environmental Type Tests

Models: RS969

1 31
Download 31 pages 20.22 Kb
Page 23
Image 23
3.7 IEEE 1613 Type Tests

3.7 IEEE 1613 Type Tests

 

IEEE Test

 

IEEE 1613

 

 

Description

 

 

Test Levels

 

 

 

 

Clause

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C37.90.3

9

 

 

ESD

Enclosure Contact

 

+/- 8kV

 

 

 

Enclosure Air

 

+/- 15kV

 

 

 

 

 

 

 

 

 

C37.90.2

8

 

 

Radiated RFI

Enclosure ports

 

35 V/m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal ports

 

+/- 4kV @ 2.5kHz

 

C37.90.1

7

 

 

Fast Transient

D.C. Power ports

 

+/- 4kV

 

 

 

A.C. Power ports

 

+/- 4kV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Earth ground ports

 

+/- 4kV

 

 

 

 

 

 

 

Signal ports

 

2.5kV common mode @ 1MHz

 

C37.90.1

7

 

 

Oscillatory

D.C. Power ports

 

2.5kV common & differential mode @ 1MHz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A.C. Power ports

 

2.5kV common & differential mode @ 1MHz

 

 

 

 

 

 

 

Signal ports

 

5 kV (Failsafe Relay)

 

C37.90

6

 

 

H.V. Impulse

D.C. Power ports

 

5 kV

 

 

 

 

 

 

 

A.C. Power ports

 

5 kV

 

 

 

 

 

 

 

Signal ports

 

2kV AC(Failsafe Relay)

 

C37.90

6

 

 

Dielectric Strength

D.C. Power ports

 

2kV AC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A.C. Power ports

 

2kV AC

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

If the unit contains copper ports the IEEE 1613 conformance is Class 1 (During disturbance errors may occur but recovery is automatic).

If the unit contains all fiber ports the IEEE 1613 conformance is Class 2 (During disturbance no errors will occur).

3.8 IEC Environmental Type Tests

Test

Description

Test Levels

Severity

Levels

IEC 60068-2-1

IEC 60068-2-2

IEC 60068-2-30

IEC 60255-21-1

IEC 60255-21-2

IEC 60529 (IPx6)

IEC 60529 (IPx7)

IEC 60529 (IP6x)

Cold Temperature

Dry Heat

Humidity (Damp Heat,

Cyclic)

Vibration

Shock

Ingress Protection Ingress Protection

Ingress Protection

Test Ad

Test Bd

Test Db

Tests Fc

Tests Ea

Water Jet

Water Submersion

Dust Talcum

-40 deg. C, 16 Hours

+85 deg. C, 16 Hours

95% (non-condensing), 55°C, 6 cycles

2g @ (10-150) Hz

30g @ 11 ms

100l/m @ 2.5m as per 14.2.6 30 min @ 1m as per 14.2.7

2kg/m3 for 8h as per 13.4

N/A

N/A

N/A

Class 2

Class 2

N/A

N/A

Cat. 1&2

23

2008 RuggedCom Inc. All rights reserved

Rev104

Page 23