5. EMI And Environmental Type Tests

Test

 

Description

Test Levels

IEEE C37.90.3

ESD

 

Enclosure Contact

+/-2kV, +/-4kV, +/- 8kV

 

 

 

 

Enclosure Air

+/-4kV, +/-8kV, +/-15kV

 

 

 

 

 

 

 

 

IEEE C37.90.2

Radiated RFI

 

Enclosure ports

35 V/m

 

 

 

 

 

 

 

 

Signal ports

+/- 4kV @ 2.5kHz

 

 

 

 

 

IEEE C37.90.1

Fast Transient

 

D.C. Power ports

+/- 4kV

 

 

 

 

 

 

 

 

Earth ground ports

+/- 4kV

 

 

 

 

 

IEEE C37.90.1

Oscillatory

 

Signal ports

2.5kV common mode @1MHz

 

 

 

 

D.C. Power ports

2.5kV common, 1kV diff. mode@1MHz

 

 

 

 

 

 

 

 

IEEE C37.90

H.V. Impulse

 

Signal ports

5kV (Fail-Safe Relay output)

 

 

 

 

D.C. Power ports

5kV

 

 

 

 

 

 

 

 

IEEE C37.90

Dielectric Strength

 

Signal ports

2kVAC

 

 

 

 

D.C. Power ports

2kVDC

 

 

 

aMeets Class 2 requirements for an all-fiber configuration. Meets Class 1 requirements for copper ports.

Table 5.2. IEEE 1613 (C37.90.x) EMI Immunity Type Testsa

Test

Description

 

Test Levels

IEC 60068-2-1

Cold Temperature

 

Test Ad

-40°C, 16 Hours

 

 

 

 

 

IEC 60068-2-2

Dry Heat

 

Test Bd

+85°C, 16 Hours

 

 

 

 

 

IEC 60068-2-30

Humidity (Damp Heat, Cyclic)

 

Test Db

95% (non-condensing), 55°C , 6 cycles

 

 

 

 

 

IEC 60255-21-1

Vibration

 

2g @ (10 - 150) Hz

 

 

 

 

IEC 60255-21-2

Shock

 

30g @ 11mS

 

 

 

 

 

Table 5.3. Environmental Type Tests