NOTICE: All pipe, fittings, solvent cement, primers and procedures must conform to American National Standards Institute and American Society for Testing and Materials (ANSI/ASTM) standards.

Soffit vents

4'

4'

Inside

 

 

 

corner

 

 

 

Electric

 

4'

Fresh

meter

 

18"

air

 

18"

4'

intake

 

 

3' above

 

 

 

 

 

 

if within 10'

4'

12" (Above grade/snow level)

window or vent

Horizontal Vent Terminal Location

The location of the vent terminal depends on the following minimum clearances and considerations (see illustration):

Vent Terminal must be at least twelve (12) inches above grade level and above normal

snow levels.

Vent Terminal must be at least four (4) feet below, or four

(4)feet horizontally from any door, operable window, soffit, under eave vent or gravity air inlet to the building or other appliances, or from gas or electric meters. Do not locate vent above walkways, doors, windows, air inlets, gas or electric meters or other equipment.

Vent Terminal must be at least three (3) feet above any forced air inlet located within ten (10) feet. Any fresh or make-up air inlet such as for a dryer or furnace area is considered to be a forced air inlet.

Vent Terminal must be at least eighteen (18) inches from an inside corner formed by two exterior walls.

Additional Considerations

Caulk

Do Not install vent terminal under any patio or deck.

Inside corner

If soffit vent is too close, block off and install new vent at another location

Caulk

6' caulk zone

Rising moisture will collect under eaves

6'

6' (1.83 m) caulk

zone or to edge ofCaulk window etc., starting

within 6'

To help prevent moisture from freezing on walls and under eaves, do not locate vent terminal on the side of a building­ with prevailing winter winds.

When terminating the vent pipe through brick or masonry surfaces, a rust-resistant sheet metal backing plate behind the vent termination is recommended.

(See illustration.)

Do Not locate vent terminal too close to shrubbery, as flue gasses may damage them.

 

 

 

4'

22ftft. sq. sq. sheet. sheetmetalmetalpl teplateon on brick or

 

brick

onary surface is recomended.

 

 

masonrysurface is recommended.

 

 

 

 

WARNING: Moisture in the flue gas will condense as it leaves the vent terminal. In cold weather this condensate can freeze on the exterior wall, under the eaves and on surrounding objects. Some discoloration to the exterior of the building is to be expected. However, improper location or installation can result in severe damage to the structure or exterior finish of the building

Caulk all cracks, seams and joints within six (6) feet of vent terminal.

All painted surfaces should be primed to lessen the chance of physical damage. Painted surfaces will require maintenance.

Insulate vent pipe exposed to cold conditions (attics, crawl spaces, etc.) with inflammable material to help prevent moisture from accumulating in vent pipe.

Do Not extend exposed vent pipe outside of building.

15

Page 15
Image 15
Ruud AP14236 installation instructions Horizontal Vent Terminal Location, Additional Considerations

AP14236 specifications

Ruud AP14236 is a highly efficient air conditioning unit that stands out in the residential HVAC market for its remarkable performance and innovative technology. This model is specifically engineered to provide optimal cooling and heating solutions, offering homeowners comfort year-round while also emphasizing energy efficiency.

One of the key features of the Ruud AP14236 is its efficiency rating, showcased by its SEER (Seasonal Energy Efficiency Ratio) rating, which provides users with an indication of energy consumption versus cooling output. With ratings often exceeding 14, the unit is designed to reduce energy bills significantly while maintaining a comfortable indoor environment. In addition to SEER, the unit boasts an HSPF (Heating Season Performance Factor) that guarantees excellent performance during colder months.

The Ruud AP14236 utilizes advanced inverter technology that allows for variable speed operation. This technology enables the air conditioner to adjust its cooling output based on the actual temperature in the home, leading to lower energy consumption while ensuring that the desired climate is reached swiftly and efficiently. This feature not only enhances comfort but also prolongs the lifespan of the unit, as it does not require the constant on-off cycling seen in traditional systems.

Equipped with an enhanced filtration system, the Ruud AP14236 significantly improves indoor air quality by capturing dust, allergens, and other particulates. This characteristic is particularly advantageous for those with allergies or respiratory conditions, as it creates a healthier living environment.

Durability is another hallmark of the Ruud AP14236, featuring robust construction materials designed to withstand the rigors of varied weather conditions. The unit's cabinet is often galvanized and treated to resist rust, ensuring longevity and reducing maintenance issues.

Noise reduction is also a primary focus in the design of Ruud AP14236. The unit operates quietly, allowing for comfortable living spaces without the disruptive sounds commonly associated with air conditioning systems. This is achieved through sound-dampening technology and acoustic insulation.

In summary, the Ruud AP14236 is engineered for energy efficiency, versatility, durability, and quiet operation. Homeowners seeking a reliable and efficient air conditioning solution will find that this unit meets their needs while providing year-round comfort and improved air quality.