Preparation

Step1.1 Choosing the installation location

If using a multi system, install as described in the installation manual supplied with the outdoor unit.

Overview of installation location requirements

 

 

100 mm or more

125 mm

 

125 mm

or more

 

or more

 

 

 

Drain hose hole

You can select the direction of

draining (left or right).

Maximum pipe height: 8/15 m

Maximum pipe length: 15/30 m

Make at least one round to reduce noise and vibration.

The actual units may look different from the images depicted here.

 

 

 

(Unit : m)

Model

 

Pipe length

Pipe height

Minimum Maximum

Maximum

 

**07*******

3

15

8

**09*******

**12*******

 

 

 

**18*******

3

30

15

**24*******

 

 

 

Outdoor

 

Make a U-trap (A) on the pipe

Unit

CAUTION

(which is connected to the indoor

Outerwall

 

unit) at outerwall and cut the

Indoor

 

bottom part of the insulation

 

(about 10 mm) to prevent

Unit

 

rainwater from getting inside

Cut insulation to have

 

through the insulation.

 

 

 

rainwater drained

 

 

 

CAUTION

Comply with the length and height limits described in the figure above.

Minimum clearances for the outdoor unit

 

 

Wall

 

 

 

 

Minimum clearance in mm

 

 

 

 

300

 

 

 

600

 

 

 

 

Air flow direction

 

 

 

Top view

Side view

 

When installing 1 outdoor unit

 

(6 cases)

 

 

 

 

(Unit: mm)

 

 

300

 

1500

300

 

 

2000

1500

 

150

600

 

 

500

300

 

 

300

 

 

 

 

 

 

 

1500

Installation

English 5