Samsung MH026FNCA service manual Apply the power to the outdoor unit

Models: MH026FNCA

1 108
Download 108 pages 7.51 Kb
Page 73
Image 73
2.2.Apply the power to the outdoor unit.

Troubleshooting

2.2.Apply the power to the outdoor unit.

Outdoor unit will try to communicate the number of indoor units specified by SW01 on outdoor display PCB.

Does LED show "Normal display"?

"Normal display" means, right 2 digit of LED on Display PCB displays '00' and left 2 digit of LED displays indoor unit address number.

No

Is error code started with '' Manual background ''

displayed on the LED?

Yes

Check the indoor unit, outdoor unit or wiring

according the error code table.

Yes

No

OK : This number is displayed

only while communicating, so each number is displayed for a short time in order.

Nothing is displayed on the LED.

Check the power source, power cable & FUSE on the outdoor unit.

2.Pipe Checking Operation (Auto Addressing Mode)

Automated checking of pipe connection (Auto addressing option)

Turn on the outdoor unit and wait for one minute.

During these 60 seconds,the left display DIS01 will show sequentially

00-01-02-03-...15-00.

E199 is showed on the display PCB of outdoor unit.

-It means you didn’t do “Pipe check operation “

Push [K1 ] button on the display PCB of outdoor unit once, then begins to start “Pipe check operation ” with displaying as below.2.

Button [K1] times

DIS 01

DIS 02

Display

[DIS 01 ] is flickering on the setting time.

 

Outdoor Temperature

Time duration

32˚F or more

less tha 32˚F

 

 

(Cool mode)

(Heat mode)

 

 

 

 

 

5min~10min

20min~50min

 

 

 

9-3

Samsung Electronics

Page 73
Image 73
Samsung MH026FNCA service manual Apply the power to the outdoor unit