Troubleshooting
| Contents |
| |
Q1 | Indoor units address SW setting correct, but outdoor unit’s PCB displayed E201 Error Code. | ||
|
|
|
|
| Check point |
| Remarks |
Analysis | Indoor unit’s sub PCB address SW or sub PCB is |
|
|
connected by mistake. |
|
| |
|
|
| |
|
|
|
|
Step 1 | Check to indoor unit’s sub PCB wire connecting |
| Indoor |
condition.(misconnecting or Sub PCB is out of order) |
| Sub PCB | |
|
| ||
|
|
|
|
Step 2 | Address setting mode change to auto address setting. |
|
|
|
|
|
|
Step 3 | Following auto address setting steps. |
|
|
|
|
|
|
Guidance | Manual Address setting is Option in FJM PLUS A. |
| |
But we solved problem like this situation, with auto address setting. |
| ||
|
| ||
|
|
|
|
- Auto address setting
| Contents |
| ||
Q1 | When the pipe checking operation is finished, outdoor sub PCB display E190 Error code. | |||
|
|
|
| |
| Check point |
| Remarks | |
Analysis | Outdoor unit fails to search indoor units or to check | The pipe checking operation | ||
indoor address. | ||||
|
|
| ||
|
|
|
| |
Step 1 | Whether The gas and liquid pipes are crossed with |
| Pipe connecting | |
each other, check to connecting. |
| |||
|
|
| ||
|
|
|
| |
Step 2 | Check to outdoor unit’s EEV coil being connected in |
| EEV Coil | |
proper location. |
| |||
|
|
| ||
|
|
|
| |
Step 3 | Check to indoor unit’s sensor being connected in |
| Indoor sensor | |
proper location. |
| |||
|
|
| ||
|
|
|
| |
Guidance | During the pipe checking operation , system check temperature change of | indoor Heat exchanger.In case, indoor | ||
sensor defect, EEV coil connector detach, malfunction of EEV, Leakage of Refrigerant, and etc can make this case. | ||||
| ||||
|
|
|
|
- Address setting another case
| Contents |
| ||
Q1 | When the pipe checking operation is finished, outdoor sub PCB display E190 Error code. | |||
|
|
|
| |
| Check point |
| Remarks | |
Analysis | Outdoor unit fails to search indoor units or to check | The pipe checking operation | ||
indoor address. | ||||
|
|
| ||
|
|
|
| |
Step 1 | Whether The gas and liquid pipes are crossed with |
| Pipe connecting | |
each other, check to connecting. |
| |||
|
|
| ||
|
|
|
| |
Step 2 | Check to outdoor unit’s EEV coil being connected in |
| EEV Coil | |
proper location. |
| |||
|
|
| ||
|
|
|
| |
Step 3 | Check to indoor unit’s sensor being connected in |
| Indoor sensor | |
proper location. |
| |||
|
|
| ||
|
|
|
| |
Guidance | During the pipe checking operation , system check temperature change of | indoor Heat exchanger.In case, indoor | ||
sensor defect, EEV coil connector detach, malfunction of EEV, Leakage of Refrigerant, and etc can make this case. | ||||
| ||||
|
|
|
|