Samsung MH026FNCA service manual 10-3-2MH080FXCA4A, Samsung Electronics, 10-6

Models: MH026FNCA

1 108
Download 108 pages 7.51 Kb
Page 94
Image 94
10-3-2 MH080FXCA4A

Reference for Installation

10-3-2 MH080FXCA4A

Refill an air conditioner with refrigerant when refrigerant has been leaked at installing or using.

1) Purge air(for new installation only).

2)Turn the 5/8" service valve clockwise to close, connect the pressure gauge (low pressure side) to the service valve, and open the 5/8" service valve again.

3)Connect the tank to refill with refrigerant.

4)Set the unit to cool operation mode.

5)Check the pressure indicated by the pressure gauge(low pressure side).

* Standard pressure is should be 8.0~9.0kg/cm2 in a regular, high operation mode.

6)Open the refrigerant tank and fill with refrigerant until the rated pressure is reached.

* It is recommended not to pour the refrigerant in too quickly, but gradually while operating a pressure valve.

7)Stop operation of the air conditioner.

8)Close the 5/8" service valve, disconnect the pressure gauge, and open the 5/8" service valve again.

9)Close the cap of each valve.

 

Suspension hook

Compound

High

pressure

gauge

gauge

 

 

Hand

 

wheel

 

Finger tight

 

fittings

For mounting

Connected to

high pressure

other and of

side

hose when

not in use

Charging line

 

Samsung Electronics

10-6

Page 94
Image 94
Samsung MH026FNCA service manual 10-3-2MH080FXCA4A, Samsung Electronics, 10-6