Sanyo CL1271, C1271, CL0971, C0971 Checking the Indoor and Outdoor Units, Replace the controller

Models: CL0971 C1271 C0971 CL1271

1 108
Download 108 pages 37.94 Kb
Page 42
Image 42

(2)If the self-diagnostics function fails to operate Check the indoor unit.

Is the fuse blown?

Normal

Replace the controller.

No indicators illuminate and the indoor fan does not rotate. Check the power voltage.

Blown

Replace the circuit board or the fuse.

9-3. Checking the Indoor and Outdoor Units

(1) Checking the indoor unit

No.

Control

Check items (unit operation)

1

Use the remote controller to operate the

The rated voltage must be present between inter-unit wirings 1 and 2.

 

unit in "TEST run" mode. To determine

Connect a 5 k ohm resistor between inter-unit wirings 2 and 3. When the

 

whether the mode is currently in

voltage at both ends is measured, approximately 12 to 15V DC must

 

"TEST run" mode, check the 4 indicator

be output and the multimeter pointer must bounce once every 8

 

lamps on the unit. If all 4 are blinking,

seconds.

 

the current mode is "TEST run."

Or instead of measuring the voltage, you can insert an LED jig and

 

 

check that the LED flickers once every 8 seconds.

If there are no problems with the above, then check the outdoor unit.

For the "Test run" procedure, refer to the Appendix B "Installation Instructions".

(2) Checking the outdoor unit

 

 

 

 

No.

Control

Check items (unit operation)

1 Apply the rated voltage between outdoor

The control panel LED (red) must illuminate.

 

unit terminals L and N.

 

2Short-circuit the outdoor unit COM terminal The compressor and fan motor must all turn on. to the T-RUN terminal.

If there are no problems with the above, then check the indoor unit.

Using the TEST/T-RUN terminals

 

TEST/T-RUN terminals

 

 

 

 

 

 

 

 

 

 

T-RUN : Test run (compressor and fan motor turn ON).

 

 

 

 

 

 

 

 

 

 

TEST/MV : Compresses time to 1/60th (accelerates

 

 

 

 

 

 

 

 

 

 

operation by 60 times faster than normal).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(TEST)/MV

 

T-RUN

 

COM

42

Page 42
Image 42
Sanyo CL1271, C1271 Checking the Indoor and Outdoor Units, Replace the controller, Replace the circuit board or the fuse