Schneider Electric 5000, 3000 Services, bits per second 9 data - bits 9 parity - none 9 stop bit

Models: 3000 5000

1 19
Download 19 pages 13.16 Kb
Page 12
Image 12

Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV.

If circuit standard cannot be confirmed, use a contact closure switch.

Use one of the following cable types to connect the UPS to the EPO switch:

CL2: Class 2 cable for general use

CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.

CL2R: Riser cable for use in a vertical run in a floor to floor shaft.

CLEX: Limited use cable for use in dwellings and for use in raceways.

For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable).

TERMINAL MODE TO CONFIGURE UPS PARAMETERS

3000 VA models:

Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS. Connect the serial cable to the serial com connector on the back of the UPS.

1.EXIT the PowerChute Business Edition using the following steps:

From the Desktop, go to Start => Settings => Control Panel => Administrative Tools =>

Services.

Select PCBE Server and PCBE Agent – right click the mouse and select Stop.

2.Open a terminal program. Example: HyperTerminal

From the Desktop, go to Start => Programs => Accessories => Communication =>HyperTerminal.

3.Double-click on the HyperTerminal icon.

Follow the prompts to choose a name and select an icon. Disregard the message, “...must install a modem,” if it is displayed. Click OK.

Select the COM port that is connected to your UPS. The port settings are:

9bits per second - 2400

9data - bits 8

9parity - none

9stop bit - 1

9flow control - none

Press ENTER

4.Example for setting the number of external battery packs (SURT192XLBP):

Once the blank terminal window is open, follow these steps to enter the number of battery packs:

Press ENTER to initiate terminal mode. Follow the prompts:

Press 1 to modify UPS Settings. Press e (or E) to modify the number of battery packs. Enter the number of battery packs, including the internal battery pack (Number of packs: 1= internal battery module, 2 = 1 SURT192XLBP,

3 = 2 SURT192XLBP, etc.). Press ENTER.

Follow the prompts.

5.Exit the terminal program.

10

Page 12
Image 12
Schneider Electric 5000, 3000 Services, bits per second 9 data - bits 9 parity - none 9 stop bit, flow control - none