6 Siemens Building Technologies,Inc.
2
Applications

Basic Operation

The Unit Vent Controller0 to 10V Output provides Direct Digital Control (DDC) technology
for unit ventilator applications. The applications available in this controller are as follows:
Heating and/or Chilled Water Cooling,
ASHRAE Cycles l and II
Application 2281
Heating and/or Chilled Water Cooling,
ASHRAE Cycle III
Application 2283
Heating and DX Cooling,
ASHRAE Cycles I and II
Application 2284
Heating and DX Cooling,
ASHRAE Cycle III
Application 2286
Nesbitt Cycle W Application 2287
Slave Mode (no control; available for set up,
and point extension device)
Application 2299

Control Temperature Setpoints

The controller maintains a specified temperature setpoint based on Day/Night mode, the
heating/cooling mode, or the setpoint dial (if used).

Day/Night Mode

The controller maintains the specified day setpoint temperature during daytime hours and the
specified night setpoint at night.
Day Heating Operation
The controller maintains the room temperature by resetting the unit ventilator's discharge
temperature setpoint (2281/2284), modulating the available coil control device, controlling
auxiliary radiation (if provided), positioning the outdoor air or face-bypass damper.