Point Database
This chapter presents a description of the Unit Vent Controller database including point descriptors, point addresses, and a listing of applications in which each point is found.
|
|
| Table 3. Point Database. | |
Descriptor | Address | Application |
| Description |
|
|
|
|
|
CTLR ADDRESS | 01 | 2281, 2283, |
| Identifies the controller on the FLN trunk. |
|
| 2284, 2286, |
|
|
|
| 2287, 2299 |
|
|
|
|
|
|
|
APPLICATION | 02 | 2281, 2283, |
| The identification number of the program running in the |
|
| 2284, 2286, |
| controller. |
|
| 2287, 2299 |
| Valid entries: 2281, 2283, 2284, 2286, 2287, 2299 |
|
|
|
|
|
ROOM TEMP | 04 | 2281, 2283, |
| Actual reading from the room temperature sensor. |
|
| 2284, 2286, |
|
|
|
| 2287, 2299 |
|
|
HEAT.COOL | 05 | 2281, 2283, |
| Current mode of operation for applications that can be either a |
|
| 2284, 2286, |
| heating mode or a cooling mode. |
|
| 2287 |
|
|
|
|
|
|
|
DAY CLG STPT | 06 | 2281, 2283, |
| The temperature setpoint in degrees that the controller |
|
| 2284, 2286, |
| maintains, during day periods in cooling mode, if a room |
|
| 2287 |
| temperature sensor setpoint dial is not present or is not used. |
|
|
|
| Refer to STPT DIAL (Point 14). |
|
|
|
| Valid entry range: 48° to 95°F (9°- 35°C) |
|
|
|
|
|
DAY HTG STPT | 07 | 2281, 2283, |
| The temperature setpoint in degrees that the controller |
|
| 2284, 2286, |
| maintains during day periods in heating mode if a room |
|
| 2287 |
| temperature sensor setpoint dial is not present or is not used. |
|
|
|
| Refer to STPT DIAL (Point 14). |
|
|
|
| Valid entry range: 48° to 95°F (9° to 35° C) |
|
|
|
|
|
NGT CLG STPT | 08 | 2281, 2283, |
| The temperature setpoint in degrees that the controller |
|
| 2284, 2286, |
| maintains during night periods in cooling mode. |
|
| 2287 |
| Valid entry range: 48° to 95°F (9° to 35°C) |
NGT HTG STPT | 09 | 2281, 2283, |
| The temperature setpoint in degrees that the controller |
|
| 2284, 2286, |
| maintains during night periods in heating mode. |
|
| 2287 |
| Valid entry range: 48° to 95°F (9°to 35°C) |
|
|
|
|
|
OADPR MINPOS | 10 | 2281, 2283, |
| The minimum position the damper will be commanded to during |
|
| 2284, 2286, |
| day mode. |
|
| 2287 |
|
|
|
|
|
|
|