APOGEE Heat Pump
Descriptor | Address | Application | Description |
|
|
|
|
CLG OUTPUT | 61 | 2281, 2283, | If the cooling control device is not DX, then the value of this |
|
| 2284, 2286, | point indicates the position of the cooling actuator. If DX cooling |
|
| 2287 | is used, then the value of this point determines whether DX is |
|
|
| ON or OFF. |
|
|
| Valid values: 0 to 100% |
|
|
|
|
OA DMPR POS | 62 | 2281, 2283, | Indicates the position of the outdoor air damper actuator. |
|
| 2284, 2286, |
|
|
| 2287 |
|
CLG P GAIN | 63 | 2281, 2283, | The proportional gain value for the cooling temperature control |
|
| 2284, 2286, | loop. |
|
| 2287 |
|
|
|
|
|
CLG l GAIN | 64 | 2281, 2283, | The integral gain value for the cooling temperature control loop. |
|
| 2284, 2286, |
|
|
| 2287 |
|
|
|
|
|
CLG D GAIN | 65 | 2281, 2283, | The derivative gain value for the cooling temperature control |
|
| 2284, 2286, | loop. |
|
| 2287 |
|
|
|
|
|
CLG BIAS | 66 | 2281, 2283, | The biasing of the cooling temperature control loop. Refer to |
|
| 2284, 2286, | CLG LOOPOUT (Point79). |
|
| 2287 |
|
|
|
|
|
HTG P GAIN | 67 | 2281, 2283, | The proportional gain value for the heating temperature control |
|
| 2284, 2286, | loop. |
|
| 2287 |
|
|
|
|
|
HTG l GAIN | 68 | 2281, 2283, | The integral gain value for the heating temperature control loop. |
|
| 2284, 2286, |
|
|
| 2287 |
|
|
|
|
|
HTG D GAIN | 69 | 2281, 2283, | The derivative gain value for the heating temperature control |
|
| 2284, 2286, | loop. |
|
| 2287 |
|
HTG BIAS | 70 | 2281, 2283, | The biasing of the heating temperature control loop. Refer to |
|
| 2284, 2286, | HTG LOOPOUT (Point 80). |
|
| 2287 |
|
|
|
|
|
ROOM P GAIN | 71 | 2281, 2284 | The proportional gain value for the room control loop. |
|
|
|
|
ROOM I GAIN | 72 | 2281, 2284 | The integral gain value for the room control loop. |
|
|
|
|
ROOM D GAIN | 73 | 2281, 2284 | The derivative gain value for the room control loop. |
|
|
|
|
ROOM BIAS | 74 | 2281, 2284 | The biasing of the room loop output point, DISCH STPT (Point |
|
|
| 93). |
CMP MIN OFF | 75 | 2284, 2286, | The minimum time, in minutes, which the unit ventilator's |
|
| 2287 | compressor will remain OFF before turning ON again. |
|
|
| Valid input: 0 to 255 minutes |
|
|
|
|
CMP MlN ON | 76 | 2284, 2286, | The minimum time, in minutes, which the unit ventilator's |
|
| 2287 | compressor will remain ON before turning OFF again. |
|
|
| Valid input: 0 - 255 minutes |
AUX LOOPOUT | 77 | 2281, 2284 | The control loop output value that is used to determine AUX |
|
|
| OUTPUT (Point 55). |
|
|
|
|
28 | Siemens Building Technologies, Inc. |