Siemens 125-1957 CLG Output, OA Dmpr POS, CLG P Gain, CLG D Gain, CLG Bias, HTG P Gain, HTG Bias

Models: 125-1957

1 48
Download 48 pages 111 b
Page 38
Image 38

APOGEE Heat Pump Controller—Multi Stage Owner's Manual

Descriptor

Address

Application

Description

 

 

 

 

CLG OUTPUT

61

2281, 2283,

If the cooling control device is not DX, then the value of this

 

 

2284, 2286,

point indicates the position of the cooling actuator. If DX cooling

 

 

2287

is used, then the value of this point determines whether DX is

 

 

 

ON or OFF.

 

 

 

Valid values: 0 to 100%

 

 

 

 

OA DMPR POS

62

2281, 2283,

Indicates the position of the outdoor air damper actuator.

 

 

2284, 2286,

 

 

 

2287

 

CLG P GAIN

63

2281, 2283,

The proportional gain value for the cooling temperature control

 

 

2284, 2286,

loop.

 

 

2287

 

 

 

 

 

CLG l GAIN

64

2281, 2283,

The integral gain value for the cooling temperature control loop.

 

 

2284, 2286,

 

 

 

2287

 

 

 

 

 

CLG D GAIN

65

2281, 2283,

The derivative gain value for the cooling temperature control

 

 

2284, 2286,

loop.

 

 

2287

 

 

 

 

 

CLG BIAS

66

2281, 2283,

The biasing of the cooling temperature control loop. Refer to

 

 

2284, 2286,

CLG LOOPOUT (Point79).

 

 

2287

 

 

 

 

 

HTG P GAIN

67

2281, 2283,

The proportional gain value for the heating temperature control

 

 

2284, 2286,

loop.

 

 

2287

 

 

 

 

 

HTG l GAIN

68

2281, 2283,

The integral gain value for the heating temperature control loop.

 

 

2284, 2286,

 

 

 

2287

 

 

 

 

 

HTG D GAIN

69

2281, 2283,

The derivative gain value for the heating temperature control

 

 

2284, 2286,

loop.

 

 

2287

 

HTG BIAS

70

2281, 2283,

The biasing of the heating temperature control loop. Refer to

 

 

2284, 2286,

HTG LOOPOUT (Point 80).

 

 

2287

 

 

 

 

 

ROOM P GAIN

71

2281, 2284

The proportional gain value for the room control loop.

 

 

 

 

ROOM I GAIN

72

2281, 2284

The integral gain value for the room control loop.

 

 

 

 

ROOM D GAIN

73

2281, 2284

The derivative gain value for the room control loop.

 

 

 

 

ROOM BIAS

74

2281, 2284

The biasing of the room loop output point, DISCH STPT (Point

 

 

 

93).

CMP MIN OFF

75

2284, 2286,

The minimum time, in minutes, which the unit ventilator's

 

 

2287

compressor will remain OFF before turning ON again.

 

 

 

Valid input: 0 to 255 minutes

 

 

 

 

CMP MlN ON

76

2284, 2286,

The minimum time, in minutes, which the unit ventilator's

 

 

2287

compressor will remain ON before turning OFF again.

 

 

 

Valid input: 0 - 255 minutes

AUX LOOPOUT

77

2281, 2284

The control loop output value that is used to determine AUX

 

 

 

OUTPUT (Point 55).

 

 

 

 

28

Siemens Building Technologies, Inc.