Application 2299 – Slave Mode
Descriptor | Address | Application | Description |
|
|
|
|
DX | 44 | 2284, 2286, | The actual status of the DX cooling compressor. |
|
| 2287 |
|
DO 5 | 45 | 2287, 2299 | Digital output 5 controls a 24 Vac load with an ON or OFF |
|
|
| status. |
EHEAT 1 | 45 | 2281, 2283, | The actual status of the first stage of electric heat. |
|
| 2284, 2286 |
|
|
|
|
|
DO 6 | 46 | 2287, 2299 | Digital output 6 controls a 24 Vac load with an ON or OFF |
|
|
| status. |
EHEA T 2 | 46 | 2281, 2283, | The actual status of the second stage of electric heat. |
|
| 2284, 2286 |
|
|
|
|
|
DO 7 | 47 | 2287, 2299 | Digital output 7 controls a 24 Vac load with an ON or OFF |
|
|
| status. |
EHEAT 3 | 47 | 2281, 2283, | The actual status of the third stage of electric heat. |
|
| 2284, 2286 |
|
|
|
|
|
DO 8 | 50 | 2299 | Digital output 8 controls a 24 Vac load with an ON or OFF |
|
|
| status. |
FAN | 50 | 2281, 2283, | This point is a digital output used to control the fan. ON |
|
| 2284, 2286, | indicates that the DO is energized; OFF indicates that the DO is |
|
| 2287 | |
|
|
|
|
NGT HW HTG | 53 | 2281, 2283, | YES indicates that the heating valve will be kept open in night |
|
| 2284, 2286, | mode in both heating and cooling modes (recommended for |
|
| 2287 | systems with hot water). NO indicates heating valve will be |
|
|
| controlled normally. |
|
|
| Valid input: YES or NO |
|
|
|
|
NGT CLG MODE | 54 | 2281, 2283, | YES indicates that night cooling is available. NO indicates that |
|
| 2284, 2286, | night cooling is not available. |
|
| 2287 | Valid input: YES or NO |
|
|
|
|
AUX OUTPUT | 55 | 2281, 2283, | Indicates the percentage of time the auxiliary radiation will be |
|
| 2284, 2286 | ON. |
|
|
| Valid values: 0 to 100% |
|
|
|
|
AUX HTG TIME | 57 | 2281, 2283, | The period of the auxiliary radiation |
|
| 2284, 2286 | algorithm. |
|
|
| Valid values: 0 to 255 minutes |
|
|
|
|
EHT STG DELY | 58 | 2281, 2283, | Delay between a stage of electric heat changing state and the |
|
| 2284, 2286 | next change of state of any stage. |
|
|
| Valid input: 0 to 255 seconds |
|
|
|
|
DO DIR.REV | 59 | 2281, 2283, | The configuration setup code for DOs. Allows the DOs to be |
|
| 2284, 2286, | direct or reverse acting (enabled equals energized or enabled |
|
| 2287, 2299, | equals |
|
|
|
|
HTG OUTPUT | 60 | 2281, 2283, | If the heating control device is a valve or |
|
| 2284, 2286, | then the value of this point indicates the position of the heating |
|
| 2287 | actuator. If electric heat is used, then the value of this point |
|
|
| determines how many stages are ON. |
|
|
| Valid values: 0 to 100% |
|
|
|
|
Siemens Building Technologies, Inc. | 27 |