Table 12: Type 38-3AH3 vacuum circuit breaker ratings (new "constant kA" ratings basis)

 

 

Measured parameter

Units

Circuit breaker type1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38-3AH3-31

38-3AH3-40

 

 

 

 

 

 

 

 

 

General

 

 

Nominal voltage class

kV

38.0

38.0

 

 

 

 

 

 

 

Rated

Rated

Maximum design voltage (V)2

kV rms

38.0

38.0

values

voltage

 

 

 

 

 

 

 

Voltage range factor (K)3

----

1.0

1.0

 

 

 

 

 

 

 

 

 

 

Insulation

Withstand

 

 

Power-frequency

kV rms

80

80

 

levels

voltage levels

 

 

 

 

 

 

 

Lightning-impulse (BIL)

kV peak

150

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated

 

 

 

Continuous4

A rms

1,200, 2,000,

1,200, 2,000,

 

current

 

 

 

 

 

3,000FC

3,000FC

 

 

Short-circuit (at rated maximum design voltage)

kA rms sym

31.5

40

 

 

 

 

 

(I)5, 6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Interrupting time7

Cycles/ms

5/83

5/83

 

 

 

 

 

 

 

 

 

Permissible tripping delay (Y)

Sec

2

2

 

 

 

 

 

 

 

Related

Current

Rated maximum design voltage (V) divided by K =

kA rms

38.0

38.0

required

 

 

 

 

(V/K)

 

 

 

 

 

 

 

 

capabilities

 

Maximum symmetrical (sym) interrupting (K x I)

kA rms sym

31.5

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

%dc component

%

47

47

 

 

 

 

 

 

 

 

 

Short-time current (K x I) (three-seconds)

kA rms sym

31.5

40

 

 

 

 

 

 

 

 

 

Closing and

 

Asymmetrical (1.55 x I)

kA rms

49

62

 

latching

 

 

 

 

 

 

 

 

 

 

 

Peak (2.6 x I)

kA peak

82

104

 

(momentary)

 

 

 

 

 

 

 

 

 

 

 

 

These ratings are in accordance with:

ANSI/IEEE C37.04-1999 Standard Rating Structure for AC High-Voltage Circuit Breakers

ANSI/IEEE C37.06-2009 AC High- Voltage Circuit Breakers Rated on a Symmetrical Current Basis - Preferred Ratings and Related Required Capabilities

ANSI/IEEE C37.09-1999 Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis

ANSI/IEEE C37.010-1999 Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis.

Footnotes:

1"xxxx" in type designation refers to the continuous current rating 1,200, 2,000 or 3,000 A, as appropriate. The 3,000 A fan- cooled rating is achieved using fan cooling as indicated in Footnote 4.

2Maximum design voltage the circuit breaker is designed for and the upper limit for operation.

3K is listed for informational purposes only. For circuit breakers rated on a "constant kA basis," the voltage range factor is 1.0.

43000FC indicates fan cooling is included in the switchgear structure for this rating. 3000 A rating is not available in outdoor equipment.

5All values apply to polyphase and line-to-line faults.

6Standard duty cycle is O - 0.3s - CO - 3 min. - CO.

7Three-cycle (50 ms) interrupting is optionally available.