480V Metal-Enclosed Switchgear
Weights and Dimensions
Dimensions
Siemens 480 volt switchgear can be configured in many ways by combining different section types. Up to five vertical sections plus a transition section can be shipped together as a unit. If all vertical sections are not to be shipped as a unit, specifications need to be provided that describe the limiting factors (e.g., low door or narrow hallway).
Normal indoor vertical sections are 101 in. (2565 mm) high and 60 in. (1524 mm) deep. A
The outdoor switchgear assembly contains the indoor assembly in an out- door housing. The overall height is 113 in. (2870 mm) and the depth is 119.40 in. (3033 mm).
The major assembly sections include:
JTransition Sections — used as transi- tion to liquid filled transformer or to outdoor dry type transformers.
JAuxiliary Sections — used as incom- ing bus duct or cable entrance when a main breaker is not used.
JMain Sections — used to contain main breaker and may house metering and feeder breakers.
JFeeder Sections — used to contain feeder breakers and other equipment such as instrumentation.
JTie Sections — used to contain tie breaker and other equipment such as feeder breakers.
Transition Section For Liquid Filled and Outdoor Dry Type Transformers
Table 4.18
| Dimension A | Weight |
| in Inches (mm) | in lbs. (kg) |
Outdoor | 55 (1397) | 500 (227) |
Indoor | 61 (1549) | 550 (250) |
Table 4.19 Breaker Element Weight in lbs. (kg)
| Element Type |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Operation | ||||||||||||||||||||||||
Manual | 140 | (64) | 170 | (64) | 175 | (80) | 180 | (82) | 185 | (84) | 210 | (95) | 215 | (98) | 290 | (132) | 295 | (134) | 350 | (159) | 355 | (161) | 425 | (193) |
Electrical | 150 | (68) | 180 | (82) | 185 | (84) | 190 | (86) | 195 | (89) | 220 | (100) | 225 | (102) | 300 | (136) | 305 | (139) | 360 | (164) | 365 | (166) | 445 | (202) |
Additional | 45 | (20) | 45 | (20) | 45 | (20) | 45 | (20) | 45 | (20) | 45 | (20) | 45 | (20) | 50 | (23) | 50 | (23) | 50 | (23) | 50 | (23) | 55 | (25) |
Weight for | ||||||||||||||||||||||||
Shipping |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Table 4.20 Fused Element Weight in lbs. (kg)
| Element Type |
|
|
|
|
|
|
|
|
| ||
Operation | ||||||||||||
Manual | 195 | (89) | 310 | (141) | 325 | (148) | 290c (132) | 390c | 350c (95) | 450c | 425c (193) | 475 (217)c |
Electrical | 205 | (93) | 320 | (145) | 335 | (152) | 330c (150) | (177) | 360c (100) | (205) | 445c (202) |
|
Additional | 45 | (20) | 45 | (20) | 45 | (20) | 50 (23) | 50 (23) | 45 (20) | 50 (23) | 55 (25) | 55 (25) |
Weight for | ||||||||||||
Shipping |
|
|
|
|
|
|
|
|
|
|
|
|
aFor use with
c Fuses mounted on separate drawout carriage and located in separate compartment. For total weight, add weight of breaker element and separate fuse carriage.
d For use with
4
480V Metal Switchgear- Enclosed
CSI Section 16470 | Siemens Electrical Products and Systems | 63 |
| Specification Guide |
|