480V Metal-Enclosed Switchgear
General
4
480V
Siemens
LV switchgear is typically installed in:
JIndustrial Plants — for power and lighting networks and feeders, power generation and other auxiliaries, and to provide power for machine tools and material handling equipment drivers.
JUtility and Co-generation Facilities
— for motor control centers to protect and distribute power to electrical devices such as blowers, compres- sors, fans, pumps, and motors.
JCommercial and Residential Buildings — for protection and distri- bution of power for lighting, elevators, air conditioning, blowers, fans, motors, and pumps.
Available Types:
JType R — indoor (NEMA 1)
JType SR — outdoor
J
J50 or 60Hz
JVoltages of 208, 240,480, or 600 volts
JCurrents up to 5000 amperes
Circuit breakers may be either manually or electrically operated, fused or unfused. The following designations are used:
JRL — Standard Interrupting
JRLE — Extended Interrupting
JRLI — High Interrupting
JRLF — Fused Type
Siemens Static Trip III trip units are pro- vided on all low voltage power circuit breakers, except
480 Volt
Industry Standards
Types R and SR switchgear with power circuit breakers are designed, tested and constructed in accordance with:
JANSI C37.20.1 —
JANSI C37.50 — Test Procedure for Low Voltage AC Power Circuit Breakers Used in Enclosures
JANSI C37.51 — Conformance Testing of
JApplicable standards of IEEE and
NEMA
JApplicable requirements of the National Electric Code (NEC)
JUL 1558 —
Type RL drawout circuit breakers are in accordance with:
JANSI C37.13 — Low Voltage AC Power Circuit Breakers Used in Enclosures
JANSI C37.16 — Preferred Ratings, Related Requirements, and Application for Low Voltage Power Circuit Breakers and ACPower Circuit Protectors.
JANSI C37.17 — Trip Devices for AC and General Purpose DC Low- Voltage Power Circuit Breakers.
JUL 1066 — Low Voltage AC and DC Power Circuit Breakers Used in Enclosures.
Features and modifications required by NEC are incorporated when the assembly is designated as “Service (Entrance) Equipment.”
UL Listing (Optional)
An Underwriters’ Laboratories listing mark (UL label) can be optionally supplied for each vertical section. The specific section must contain only devices which are UL Listed or are UL recognized com- ponents found suitable for the intended use. All circuit breaker drawout elements are UL Listed.
50 | Siemens Electrical Products and Systems | CSI Section 16470 | |
Specification Guide | |||
|
|