480V Metal-Enclosed Switchgear
VT, CPT, CT Data
Technical
Table 4.10 | Voltage Transformers |
|
|
|
|
| |
| Accuracy Class at 60 Hz |
|
|
| Thermal |
| |
| Burden |
|
|
|
| ||
|
|
| Rating |
| |||
Ratio | W | X | Y | Hertz | |||
Rating | VA | ||||||
600:120 | 0.6 | 0.6 | 1.2 | 100 | 150 | 50/60 | |
480:120 | 0.6 | 0.6 | 1.2 | 100 | 150 | 50/60 | |
288:120 | 0.6 | 0.6 | 1.2 | 100 | 150 | 50/60 | |
|
|
|
|
|
|
|
Table 4.11 Control Power Transformers—115°C Rise
kVA | Phase | Primary | Secondary |
Voltage | Voltage | ||
3 |
|
|
|
5 | Single | 240/480 | 120/240 |
10 a | |||
15 a |
|
|
|
aRequires complete compartment.
Table 4.12 Current Transformers for
| Accuracy at 60 Hz Metering Burden (ohms) |
|
|
| Relay | ||
Ratio |
| Class | |||||
100:5 | 1.2 | 2.4 |
| — | — | — | C5 |
150:5 | 1.2 | 2.4 |
| — | — | — | C5 |
200:5 | 1.2 | 1.2 |
| — | — | — | C10 |
250:5 | 0.6 | 1.2 |
| — | — | — | C10 |
300:5 | 0.6 | 0.6 |
| 1.2 | — | — | C10 |
400:5 | 0.6 | 0.6 |
| 1.2 | — | — | C5 |
500:5 | 0.6 | 0.6 |
| 0.6 | — | — | C10 |
600:5 | 0.3 | 0.6 |
| 0.6 | 1.2 | — | C10 |
800:5 | 0.3 | 0.3 |
| 0.6 | 0.6 | — | C15 |
1000:5 | 0.3 | 0.3 |
| 0.3 | 0.6 | 1.2 | C20 |
1200:5 | 0.3 | 0.3 |
| 0.3 | 0.6 | 1.2 | C20 |
1500:5 | 0.3 | 0.3 |
| 0.3 | 0.3 | 0.6 | C30 |
1600:5 | 0.3 | 0.3 |
| 0.3 | 0.3 | 0.6 | C30 |
2000:5 | 0.3 | 0.3 |
| 0.3 | 0.3 | 0.6 | C5 |
2500:5 | 0.3 | 0.3 |
| 0.3 | 0.3 | 0.3 | C10 |
bBreaker compartment will accept 3 CT’s
Table 4.13 Current Transformers for
| Accuracy at 60 Hz Metering Burden (ohms) |
|
|
| Relay | ||
Ratio |
| Class | |||||
1000:5 | 0.3 | 0.3 |
| 0.6 | 0.6 | 1.2 | C20 |
1200:5 | 0.3 | 0.3 |
| 0.3 | 0.6 | 1.2 | C25 |
1500:5 | 0.3 | 0.3 |
| 0.3 | 0.3 | 0.6 | C35 |
2000:5 | 0.3 | 0.3 |
| 0.3 | 0.3 | 0.3 | C25 |
2500:5 | 0.3 | 0.3 |
| 0.3 | 0.3 | 0.3 | C30 |
3000:5 | 0.3 | 0.3 |
| 0.3 | 0.3 | 0.3 | C15 |
3200:5 | 0.3 | 0.3 |
| 0.3 | 0.3 | 0.3 | C20 |
4000:5 | 0.3 | 0.3 |
| 0.3 | 0.3 | 0.3 | C10 |
5000:5 | 0.3 | 0.3 |
| 0.3 | 0.3 | 0.3 | C10 |
bBreaker compartment will accept 3 CT’s in line on lower disconnects.
cBreaker compartment will accept 6 CT’s, 3 on lower and 3 on upper disconnects.
dBreaker compartment will accept 3 CT’s in staggered arrangement, 2 on lower and 1 on upper disconnects.
4
480V Metal Switchgear- Enclosed
CSI Section 16470 | Siemens Electrical Products and Systems | 59 |
| Specification Guide |
|