480V Metal-Enclosed Switchgear

Auxiliary / Breaker Section Dimensions

Dimensions

Auxiliary Sections — Front Views

Table 4.21 Auxiliary Section Weight in lbs. (kg)

 

R22

R30

 

Indoor

1000 (455)

1200

(545)

Outdoor

2000 (909)

2400

(1091)

Dimensions in Inches (mm)

Main Breaker Sections — Front Views

Feeder Breaker Sections and Combinations — Front Views

4

480V Enclosed-MetalSwitchgear

Table 4.22 Breaker Section and Connection Weights in lbs. (kg)a

 

R22

 

R30

 

R36

Indoor

1400

(636)

1900

(864)

2210 (1005)

Outdoor

2400

(1091)

3100

(1409)

aWeights shown do not include weight of circuit breaker removeable elements. All weights are approximate based on aluminum bus. For outdoor lineup, add

1200 lb (545 kg) to total weight of individual sections for end walls and hoist.

Breaker Designations

A = RL-

800 / 1600 / 2000,

RLF-

800 / 1600 / 2000,

RLE- 800 / 2000b, RLI-800b

B = RL-

3200

C = RLF-

3200 in one cell, with

 

fuse drawout (RFC-3200)

 

in other cell

D = RLF-

4000 in one cell, with

 

fuse drawout (RFC-4000)

 

in other cell

E = RL-

4000, RLE-4000

F = RLF-

5000 in one cell with

 

fuse drawout (RFC-5000)

 

in other cell

G = RL-

5000

 

 

b22 in. (559 mm) compartment only.

Tie Breaker Sections and Combinations — Front Views

cFeeder breakers located above tie breaker must be electrically on opposite side of tie breaker from feeder breaker which is located below the breaker.

64

Siemens Electrical Products and Systems

CSI Section 16470

Specification Guide

 

 

Page 16
Image 16
Siemens 480V manual Auxiliary / Breaker Section Dimensions, Breaker Section and Connection Weights in lbs. kga