01.03

 

 

 

 

 

 

 

 

Technical Data

 

 

 

 

 

 

 

 

 

R/R unit

6SE70..-.....-1BA0

41-5EH85

42-1EH85

42-8EH85

41-3FH85

42-0FH85

42-8FH85

 

 

 

 

 

 

 

 

 

Rated voltage, rated frequency, rated current

 

 

 

 

 

 

Rated voltage

 

V

 

 

 

 

 

 

 

Rectifier connection

 

3 AC 380 to 480V +10% –15% 1)

 

3 AC 500 to 600V +10% –15%

Regenerating connection

 

 

using an (auto) transformer

 

 

 

 

 

1.2 times the voltage of the rectifier connection

 

DC link voltage

 

DC 510 to 650V +10% –15%

 

DC 675 to 810V +10% –15%

Rated frequency fn

Hz

 

 

 

 

 

 

 

Input

 

 

 

46 to 64

(automatic frequency matching)

 

Output

 

 

 

 

D.C.

 

 

 

Rated current

 

A

 

 

 

 

 

 

 

(rms value)

 

 

 

 

 

 

 

 

 

With autotransformer

 

 

 

 

 

 

 

 

Regenerating, line side

 

1400

1960

2665

 

1215

1825

2665

Regenerating, unit side

 

1170

1640

2220

 

1015

1520

2220

Rectifier operation

 

1300

1820

2470

 

1125

1690

2470

Without autotransformer

 

 

 

 

 

 

 

 

Regenerating, unit side

 

1170

1640

2220

 

1015

1520

2220

Rectifier operation

 

1300

1820

2470

 

1125

1690

2470

Load class I to EN 60146-1-1 of the DC link current (average value)

 

 

 

in rectifier operation; currents reduced to 92% in regenerating operation

 

 

Rated current

 

A

1500

2100

2850

 

1300

1950

2850

(average)

 

 

 

 

 

 

 

 

 

DC link connection

 

 

 

 

 

 

 

 

Rectifier operation

 

 

 

 

 

 

 

 

Load class II to EN 60146-1-1 of the DC link current (average value)

 

 

 

in rectifier operation; currents reduced to 92% in regenerating operation

 

 

Rated current

 

A

1380

1930

2620

 

1195

1795

2620

Base load duration

s

 

 

240

 

 

 

Excess current

 

A

2040

2860

3875

 

1770

2650

3875

Excess current duration

s

 

 

60

 

 

 

Losses, cooling

 

 

 

 

 

 

 

 

 

Power dissipation

kW

4.76

6.12

9.14

 

4.06

5.70

9.23

- Maximum

 

 

 

 

 

 

 

 

 

Cooling air requirement

l/min

 

 

54

2)

 

 

 

coolant pressure drop ∆p

bar

 

 

0.75 1)

 

 

Dimensions, weight

 

 

 

 

 

 

 

 

Width

 

mm

 

 

504

3)

 

 

Height

 

mm

 

 

740

 

 

Height

 

mm

 

 

550

 

 

 

Weight app.

 

kg

 

 

142

3)

 

 

„Parallel units“ (-1BD0 bzw. -0BD0)for connecting in parallel have the same technical data as the corresponding "basic units"(-1BA0 bzw. -0BA0). Please note the unit correspondence and notes of Section 3.7 (of the operating instructions for air-cooled rectifier units or rectifier/regenerating units)!

The permissible output current in parallel mode is reduced (due to current division between the power sections) by 10 % as compared to the sum of the rated currents of the separate power sections.

1)For units from product status A2 and onwards (labelling on the unit at the coolant connection).

2)If the cooling circuits of the two converters are connected in parallel.

3)A rectifier/regenerating unit consists of two converters in separate housings.

Siemens AG 6SE7086-4AH85-1BA0