Appendix A Technical Specifications

Overload Specifications

 

 

 

 

 

 

Overload classes

Overload classes 2 through 23 with one second increments.

Trip Characteristics

Tripping time at 6 x I FLC

= 95% of the overload class (±5%).

 

Tripping time at 1.5 x I FLC within two minutes for warm conditions for all classes.

Tripping threshold

(1.1 ± 0.05) x I FLC for motors with 1.00 service factor, and

 

(1.2 ± 0.05) x I FLC for motors with 1.15 service factor.

Tripping time

20 minutes @1.15 x I FLC

for motors with service factor 1.

Mechanical jam protection

Sudden increase of the motor running current. Pick-up current adjustable from 120 to

SAMMS-LVX only

400% in increments of 5% of I FLC . Pick-up time 360 msec.

 

Default value: 200% I FLC.

 

 

Loss of load protection

Sudden decrease of motor running current. Pick-up current adjustable from 20 to 95% in

SAMMS-LVX only

increments of 5% of I FLC . Pick-up time 360 msec.

 

Default value: 50% I FLC .

 

 

Process current warning

Settings from 0 to 100% of I FLC .

 

SAMMS-LVX only

 

 

 

 

Accuracy

± 5% of overload trip curve values.

 

 

± 2% repeat accuracy.

 

 

Phase unbalance protection

Response time after 1 second

 

 

Shifted trip threshold value to 0.9 x I FLC

at 40% phase unbalance.

Equipment ground fault protection

Response time after overload class in seconds.

 

Pick-up time: 360 msec.

 

 

 

Pick-up current:

 

 

 

Overload Relay Size Pick-up Current

Default

 

1A

1.5A

1.5A

 

1B

2A- 5A

5A

 

1C

2A- I FLC

5A

 

2A

2A- I FLC

10A

 

2B

2A- I FLC

10A

 

3

2A- I FLC

10A

 

4

2A- I FLC

10A

 

5

5A- I FLC

10A

 

6

10A- I FLC

20A

 

I FLC

is the value of I FLC for OLR#2 if F# is not set to OFF. If F3 is OFF, I FLC is the value of

 

I FLC

for OLR#1.

 

 

Ambient temperature

Motor ambient temperature adjustable 0 - 70°C in increments of 5°C.

 

Default value: 40°C.

 

 

 

 

 

 

 