Appendix A Technical Specifications
Overload Specifications |
|
|
|
|
|
| |||
Overload classes | Overload classes 2 through 23 with one second increments. | |||
Trip Characteristics | Tripping time at 6 x I FLC | = 95% of the overload class (±5%). | ||
| Tripping time at 1.5 x I FLC within two minutes for warm conditions for all classes. | |||
Tripping threshold | (1.1 ± 0.05) x I FLC for motors with 1.00 service factor, and | |||
| (1.2 ± 0.05) x I FLC for motors with 1.15 service factor. | |||
Tripping time | 20 minutes @1.15 x I FLC | for motors with service factor 1. | ||
Mechanical jam protection | Sudden increase of the motor running current. | |||
400% in increments of 5% of I FLC . | ||||
| Default value: 200% I FLC. |
|
| |
Loss of load protection | Sudden decrease of motor running current. | |||
increments of 5% of I FLC . | ||||
| Default value: 50% I FLC . |
|
| |
Process current warning | Settings from 0 to 100% of I FLC . |
| ||
|
|
|
| |
Accuracy | ± 5% of overload trip curve values. |
| ||
| ± 2% repeat accuracy. |
|
| |
Phase unbalance protection | Response time after 1 second |
| ||
| Shifted trip threshold value to 0.9 x I FLC | at 40% phase unbalance. | ||
Equipment ground fault protection | Response time after overload class in seconds. | |||
|
|
| ||
|
|
| ||
| Overload Relay Size | Default | ||
| 1A | 1.5A | 1.5A | |
| 1B | 2A- 5A | 5A | |
| 1C | 2A- I FLC | 5A | |
| 2A | 2A- I FLC | 10A | |
| 2B | 2A- I FLC | 10A | |
| 3 | 2A- I FLC | 10A | |
| 4 | 2A- I FLC | 10A | |
| 5 | 5A- I FLC | 10A | |
| 6 | 10A- I FLC | 20A | |
| I FLC | is the value of I FLC for OLR#2 if F# is not set to OFF. If F3 is OFF, I FLC is the value of | ||
| I FLC | for OLR#1. |
|
|
Ambient temperature | Motor ambient temperature adjustable 0 - 70°C in increments of 5°C. | |||
| Default value: 40°C. |
|
| |
|
|
|
|
|
43