4 Troubleshooting

Error Condition

Incomplete

Sequence

External Trip

CPU Fault

Troubleshooting Guide

Main Cause

 

Remedy

Indicates the SAMMS-LV unit does not

1. If the unit trips one second after start, verify that

detect current one second after a start

 

current transformer secondary input is present in the

command, or it detects current one

 

range of 100 mVAC to 3.54 VAC at terminals 1, 2,

second after a stop command.

 

and 3 with reference to 4. Verify that the coil voltage

 

 

is 115 VAC at terminals 14, 15, or 16 with reference

 

 

to 13 when the motor is started. Verify 115 VAC at

 

 

terminal 7 with reference to 13. Correct conditions if

 

 

necessary. Call Siemens if unit continues to trip.

 

2. If the unit trips one second after a stop command,

 

 

verify the contactor is open. Repair or replace the

 

 

contactor if it is not functioning properly.

 

3. Verify operation of mechanical interlock, and replace

 

 

or adjust.

 

4. Verify absence of voltage at terminals 1, 2, and 3 with

 

 

reference to 4, and at terminals 14, 15, or 16 with

 

 

reference to 13. If voltage is present, define the

 

 

source and reconnect so that the motor current only

 

 

passes through the current transformer.

 

5. To disable incomplete sequence, select F1 on the

 

 

HHC, press the ENTER key for one or more seconds

 

 

and start the motor. The incomplete sequence will

 

 

remain disabled until the above procedure is

 

 

repeated.

If the external trip LED is solidly

1. Jam conditions such as a blocked conveyor belt or

illuminated and the motor is stopped, it

 

gear train cause a sudden increase in motor current,

indicates a jam or loss of load

 

which can damage the motor’s insulation in a short

condition.

 

period of time.

 

2. Loss of load conditions, such as a broken blade of an

 

 

impeller or loss of back pressure of a pump, result in

 

 

a sudden decrease in motor current.

 

3. F16 on the HHC displays the external trip current at

 

 

the time of the trip.

 

 

In any case, determine the reason for the external trip

 

 

and correct the problem before restarting the motor.

 

 

If the external trip LED flashes and the motor

 

 

continues to run, it indicates loss of load warning or

 

 

process current warning.

Indicates a problem in the

 

Verify voltage between terminals 5 and 6 is more than

microprocessor or a low voltage

 

10 VAC. If fault persists, call Siemens.

condition.

 

 

 

 

 