Stabilization of Unstable Control Loops
14 MPC Level
V 1.0, Beitrags-ID: 42200753
Copyright Siemens AG 2010 All rights reserved
3.2 PID Tuner
The PCS 7 PID tuner can be used for integral processes without problems if at
least one stable controller parameterization is already available. The following hints
are helpful for this:
Fix the check mark „With integral action in the process“
Excite the process with a step in the set point in closed loop in automatic mode
Chose the proportional only controller as controller type, at least, if you want to
use this controller as slave controller in cascades (e.g. subordinated to a MPC)
or if you are not interested in exact set point tracking.
Set the MC_Offset to the value of the manipulated variable needed to reach
the typical operating point, if you know it, in order to avoid the persistent control
error at least in this operating point.