OPERATION

Repeated trial starts can over heat the motor and result in motor burnout (particularly for across the line starting). If repeated trial starts are made, allow sufficient time between trials to permit heat to dis- sipate from windings and rotor to prevent overheating. Starting cur- rents are several times running cur- rents and heating varies as the square of the current.

After installation is completed, but before motor is put into regular ser- vice, make an initial start as fol- lows:

1. Check motor connections and

VFD connections against wiring

diagrams.

2. Check voltage, phase, and all

loaded drive parameters against

a. If load is disconnected, run motor at no load long enough to be certain that no unusual conditions develop. Listen and feel for excessive noise, vibra- tion, clicking, or pounding. If present, stop motor immedi- ately. Investigate the cause and correct before putting motor in service.

b. If load is not disconnected, interrupt the starting cycle after motor has decelerated to a slow speed. Carefully observe for unusual conditions as motor coasts to a stop.

4.When checks are satisfactory, operate at minimum load and look for unusual conditions.

Increase load slowly to a maxi- mum. Check unit for satisfactory

operation.

Electric motors operating under nor- mal conditions become quite warm. Although some places may feel too hot to touch, the unit may be within operational limits. Use a thermo- couple to measure winding temper- ature when there is any concern.

The total temperature, not the tem- perature rise, is the measure of safe operation. Investigate the operating conditions if the total temperature measured by a ther- mocouple placed on the winding exceeds:

275°F (135°C) for class “F” insula- tion

302° F(150°C) for class “H” insula- tion

motor nameplate. If an auxiliary

blower is supplied, check to see

that it is wired and operating

properly. The blower should be

wired to a separate 60 hz power

source.

3. If possible, remove external load

and turn shaft by hand to ensure

free rotation. This may have

been done during installation pro-

cedure; if so, and conditions have

not changed since, this check

may not be necessary.

VFD OPERATION

Special consideration must be paid to ensure that the motor is operat- ed within recommended guidelines for torque and speed for the type and size of RGZESDI motors select- ed. Under no circumstances should the motor be operated at frequen- cies beyond the safe mechanical limits shown below in this docu- ment.

RGZESDI Constant Torque motors provide full rated torque within their listed speed range, without exceed- ing their Class F temperature rating

Maximum Safe Mechanical

Speed Limits

Direct Connected Loads

(does not imply constant horsepower capability)

Motor 3600 1800 1200

Frame rpm rpm rpm

143-184 7200 5400 2700

213-256 5400 4200 2700

284-286 5400 3600 2700

324-326 4500 3600 2700

364-365 4500 2700 2700

404-445 3600 2700 1800

447-449 3600 2250 1800

CAUTION

Electrical Overload.

May cause property damage.

To avoid the danger, guard against overloading. Overloading

causes overheating and overheating means shortened insulation

life. A motor subjected to a 10°C temperature rise above the

maximum limit for the insulation may cause the insulation life

to be reduced by 50%. To avoid overloading, be sure motor cur-

rent does not exceed nameplate current when nameplate voltage

is applied.

CAUTION

Electrical Overload.

May cause property damage.

To avoid damage to the motor, caution must be observed when applying standard motors for continuous low speed, constant torque operation. A standard motor’s self-cooling capacity depends upon self-ventilation schemes that are greatly reduced at decreased operating speeds.

CAUTION

Electrical Overload.

May cause property damage.

To avoid damage to the motor, it is the responsibility of the startup personnel during commissioning of the VFD/ motor combination to properly tune the drive to the motor for the specific application. Application of motors which are not per the guidelines of this document may void the warranty, if they are not specifically approved by Siemens.

on PWM (pulse width modulated)

designed for operation at 150% of

inverter power. Speed ranges are

rated torque for one minute, up to

based on use with vector type IGBT

the base speed of the motor (over-

inverters, set at a minimum 3 kHz

load capacity declines as the motor

switching frequency, and are

reaches maximum speed).

5

Page 5
Image 5
Siemens RGZESDI manual Electrical Overload May cause property damage, VFD Operation