2-10 Installation
Series
505 High Speed Counter
and Encoder Module User
’
s Manual
2.5 Logging the Module into the Controller2.5.1
Updating
the I/O
After inserting the module into the base, update the I/O configuration
Configuration
in the controller
. The module does
not
automatically onfigure itself.
Definition
A VPU or other programming device must be connected to the controller to
register and verify controller module communication.
2.5.2
Selecting the I/O
W
ith your VPU or other programming device, select the I/O Configuration
Configuration
option. For example, if you have the module inserted into the first slot of
the first I/O base, configure it as displayed in Figure 2-6. Refer to the
manual that came with the programming device for instructions.
I/O MODULE DEFINITION FOR :
CHANNEL 1
BASE 00
Slot Address X Y WX WY Function
I/O
Number of Bit and W
ord I/O
Special
1
2
3
4
5
6
7
8
.....
.....
.....
.....
.....
.....
.....
.....
0001
0000
0000
0000
0000
0000
0000
0000
.....
.....
.....
.....
.....
.....
.....
.....
00
00
00
00
00
00
00
00
..
..
..
..
..
..
..
..
00
00
00
00
00
00
00
00
..
..
..
..
..
..
..
..
00
00
00
00
00
00
00
..
..
..
..
..
..
..
..
00
00
00
00
00
00
00
.......
.......
.......
.......
.......
.......
.......
.......
No
No
No
No
No
No
No
No
03 05
Base Number
Displays number
of the current
base.
Slot Number
Install
the HSC into any avail
-
able I/O slot on the Series 505
base.
I/O Address
The
HSC module is logged in as
three input words (WX) and five
output words (WY).
SF Module
The HSC is not an SF
Module. The default for this
definition is
NO.
Figure 2-6
Sample I/O Definition Chart