Product Information PCS7/TM V2.02 24.10.2001
Siemens AG 2001 15 of 21
7 Creating a new PCS 7/TM project
This explanation is valid for the language selection "Germ an". Please observe the WinCC/ PCS 7
product information ("ReleaseNotes")..

7.1 Creating a Project for Multi-Client Operation on a Server

Create the project as a multi-user project with WinCC/ PCS7, > V5.0.
It must be noted here that the server name and the project name in the multi- client are both dis-
played according to the selection of the area overviews: The names of the two components should
therefore not be excessively long.
Edit the Split Screen Wizard
Edit the Alarm Logging Wizard
Insert new driver for the TELEPERM M channel in the variable managem ent.
Start DynWizEdit and read all 4 TELEPERM M wizards ("TELEPERM M Verbindung einrich-
ten.wnf", ”TELEPERM M Import ORPA.wnf”, ”TELEPERM M Import Bauste ine.wnf” and
”TELEPERM M Meldungen.wnf”) from the Siemens\WinCC\BSTMapper direc tory and create CWD
file.
Note: When activating the Split Screen Wizard (from the current version V2. 02) the current wizards
are already included in the project !
Execute wizard "TELEPERM M Verbindung einrichten" and def ine the desired connections.
Execute ”Import TELEPERM M ORPAs” once or twice (user or TML block s).
ÍPlease do not forget that importing so called field blocks (GA, GB, etc.) always only 1
element is generated; additional elements have to be defined manually before executing the
import of TELEPERM M blocks.
Execute ”Import TELEPERM M blocks”.
Execute ”TELEPERM M messages” and create default message texts.
Area-specific reporting
Using this function requires messages from function blocks (via stat us word) to be allocated to an
area in the sense of the Picture Tree Manager.
Manual allocation:
Each message concerned must be provided with an area name in the "Are a" message block.
Allocation via EXCEL list and TM_RangMeld:
To make this allocation more convenient and easier to reproduce, it ca n be performed using the
TM_RangMeld program that is provided on the WinCC/TM CD and an EXCEL list th at must be
created beforehand. See the corresponding description on the CD.
Prior to this step, you should expediently create the topmost area level in the Picture Tree Man-
ager.
If necessary, the TELEPERM M message class must be included in the se lection of the individual
message windows.
Next, all further configuration steps are performed.