Communication-capable Circuit Breakers

WL Circuit Breaker

The trigger event can be set individually for each waveform buffer. The point at which the trigger event is to take place in the waveform buffer can also be defined. This setting can be used to set the ratio of the pre-event history to the post-event history. If the pre-trigger event history is to be analyzed, the position can be set to 80%. When the event occurs, 0.8 seconds of pre- event history and 0.2 seconds of post-event history are available in the waveform buffer, and an existing COM16 module adds a time stamp to the trigger event.

Each waveform buffer stops independently, depending on the trigger event and can be activated again once the analysis is complete.

A large amount of data (approx. 25 kByte for each waveform) can be downloaded and analyzed using WinPM.Net, the BDA and the ETU776 display. Depending on the option,

a range of zoom options and export functions are available.

Voltage Transformers

For isolation reasons, a voltage transformer is used in conjunction with the Metering Function Plus module. This prevents voltage signals of up to 1kV from reaching the ETU directly via the auxiliary secondary connections.

The metering module (“Metering Function Plus”) can be set to expect 3W or 4W (LL/LG) connections and will adjust the amplitude and phase of the signal as necessary.

Three VTs must be used at all times.

All three VTs should be rated for the nominal system L-L voltage (e.g. 480V) and may have either 100V, 110V or 120V secondary voltages.

The following ratios and suggested and equivalent VTs can be used: 240:120 = 2:1

(ITI Part # 460-240 or 468-240) 480:120 = 4:1

(ITI Part # 460-480 or 468-480)

2/15

600:120 = 5:1

(ITI Part # 460-600 or 468-600)

VT Accuracy

Each Metering Module presents a purely resistive (unity power factor) load to the transformer. Assuming no other devices connected to the VT, a ITI type 486 VT can safely feed 10 metering modules and and still maintain 0.6% accuracy assuming the wiring from the VT to the individual metering modules is twisted pair and kept to a minimum length.

This data applies to ambient temperatures from 30ºC to 50ºC and a primary voltage from 80% to 120% Vn.

Maximum distance from voltage transformer

The maximum distance between the metering function and the voltage transformer depends on the cable size and the desired accuracy class.

Metering VT Settings:

Delta/Wye : Delta

VT Primary: 480 (for example)

VT Secondary: 120 (for example)

Metering VT Settings:

Delta/Wye : Delta

VT Primary: 480 (for example)

VT Secondary: 120 (for example)

For a 14AWG cable, the maximum distance should not exceed 50 m for class 0.5 and 100 m for class 3. In areas with high EMC exposure, shielded cable should be used.

Parameters for the settings of the metering function

The trip unit settings which must be made are:

1)VT Primary Voltage (240V, 480V, 600V)

2)VT Secondary Voltage (100V, 110V, 120V)

3)VT Connection (Wye / LG, Delta / LL)

The following tools and functions are available if the parameters have to be changed:

WinPM.Net

WL Config

BDA/BDA Plus

ETU776 display

Note: Required primary and secondary overcurrent protection (fusing) not shown for clarity.

WL MODBUS Communication and Electronic Accessories • January 2005

Page 26
Image 26
Siemens UL1066, UL 489 specifications Voltage Transformers, VT Accuracy, Maximum distance from voltage transformer

UL 489, UL1066 specifications

Siemens UL1066 and UL489 are essential components in the landscape of electrical equipment, specifically in circuit protection and control. These standards ensure reliability, safety, and efficiency in various applications, including industrial, commercial, and residential settings.

The Siemens UL1066 is primarily focused on disconnect switches. These devices are designed to isolate electrical circuits, ensuring the safety of both personnel and equipment during maintenance or in case of faults. One of the key features of UL1066 disconnect switches is their high breaking capacity, enabling them to handle significant fault currents without failure. This characteristic is crucial in protecting downstream equipment from damage caused by short circuits. The UL1066 switches are also known for their robust construction, often featuring a metal enclosure that enhances durability and environmental resistance. Additionally, these switches can be operated manually or remotely, offering flexibility in operation and control.

On the other hand, Siemens UL489 circuit breakers provide comprehensive protection against overcurrents and short circuits. These devices not only interrupt fault currents but also protect connected devices from damage due to overload situations. Key features of UL489 circuit breakers include adjustable trip settings, which allow users to customize the response to overcurrent conditions based on specific application requirements. This adaptability makes them suitable for a wide range of environments, from large industrial plants to smaller commercial buildings.

Both UL1066 and UL489 products are constructed with advanced technologies, such as thermal-magnetic or electronic trip mechanisms in UL489 devices, ensuring precise and timely interruption of fault currents. These technologies promote energy efficiency and stability within electrical systems. In addition, many of these devices are equipped with indication features, providing clear visual status cues for quick assessment in emergency situations.

In terms of characteristics, both UL1066 and UL489 devices adhere to rigorous testing and certification processes to meet UL standards. This compliance assures users of their performance and reliability. Furthermore, the devices are designed to accommodate a wide range of operating temperatures and environmental conditions, making them versatile choices for various applications.

In summary, Siemens UL1066 and UL489 devices are paramount in ensuring safety and efficiency in electrical circuits. Their advanced features and robust construction make them indispensable in protecting both personnel and equipment in an array of industrial and commercial applications.