Siemens UL1066, UL 489 specifications Technical data for the digital configurable output module

Models: UL 489 UL1066

1 92
Download 92 pages 35.36 Kb
Page 38
Image 38

Communication-capable Circuit Breakers

WL Circuit Breaker

The status can be read via the input module, which means that a motor could be switched ON or OFF via the

These events are available for the digital, configurable output module (part 2)

configurable digital output module.

Many other applications are also possible.

Unlike the digital output module with the rotary switch, a time delay cannot be added to the event. A setpoint can be output with a delay via the configurable digital output module, for example, if the setpoint itself is already delayed.

Like the digital output module with the rotary switch, this module also indicates the status of the outputs via the associated LEDs.

Attention: Do not power off the configurable output module within 15 seconds of changing the configuration via BDA or WinPM.Net. This could result in a red DEVICE LED and all outputs will be deactivated indicating that the device is incompletely configured.

Setpoints

Over current

Over current in neutral conductor

Over current - ground fault

Phase unbalance - current

Phase unbalance - voltage

Demand - current

Undervoltage

Overvoltage

Total harmonic distortion - current

Total harmonic distortion - voltage

Crest factor

Form factor

Under frequency

Over frequency

Active power in normal direction

Active power in reverse direction

Apparent power

Reactive power in normal direction

Reactive power in reverse direction

Power factor leading

Power factor lagging

Demand - active power

Demand - reactive power

Demand - apparent power

Waveform buffer A

Figure

The outputs can only be

configured using

2-15

appropriate software.

 

2/27

Trigger event

Waveform buffer B

Table 2-18Part 2 of the table shows all the events on the CubicleBUS that can be output via the digital configurable output module. Configuration is carried out using WinPM.Net, WL Config

or the BDA.

Technical data for the digital configurable output module

Operating voltage min. / max.

19.2V / 28.8V

Operating current min. / max. (excluding relay)

29mA / 39mA

Operating current min. / max. relay

29mA / 250mA

No. of channels per digital output module

6

Max. current rating for optocoupler output with 24V

100mA

Max. current rating for for six relay outputs with 24V DC/250V AC/250V DC

5A / 5A / 0.25A

Max current rating for one relay output with 24V DC

2.7A

Max. no. of digital configurable output modules on one WL Circuit Breaker

1

Power loss min. / max.

0.74W / 5.4W

Dimensions W / H / D

70mm / 86mm / 95mm

Weight (optocoupler / relay)

0.223 kg / 0.321 kg

Operating temperature range

-20°C / 60°C

 

 

Table 2-19This table provides technical data for the digital configurable output module on the

CubicleBUS.

WL MODBUS Communication and Electronic Accessories • January 2005

Page 38
Image 38
Siemens UL1066, UL 489 Technical data for the digital configurable output module, Trigger event Waveform buffer B

UL 489, UL1066 specifications

Siemens UL1066 and UL489 are essential components in the landscape of electrical equipment, specifically in circuit protection and control. These standards ensure reliability, safety, and efficiency in various applications, including industrial, commercial, and residential settings.

The Siemens UL1066 is primarily focused on disconnect switches. These devices are designed to isolate electrical circuits, ensuring the safety of both personnel and equipment during maintenance or in case of faults. One of the key features of UL1066 disconnect switches is their high breaking capacity, enabling them to handle significant fault currents without failure. This characteristic is crucial in protecting downstream equipment from damage caused by short circuits. The UL1066 switches are also known for their robust construction, often featuring a metal enclosure that enhances durability and environmental resistance. Additionally, these switches can be operated manually or remotely, offering flexibility in operation and control.

On the other hand, Siemens UL489 circuit breakers provide comprehensive protection against overcurrents and short circuits. These devices not only interrupt fault currents but also protect connected devices from damage due to overload situations. Key features of UL489 circuit breakers include adjustable trip settings, which allow users to customize the response to overcurrent conditions based on specific application requirements. This adaptability makes them suitable for a wide range of environments, from large industrial plants to smaller commercial buildings.

Both UL1066 and UL489 products are constructed with advanced technologies, such as thermal-magnetic or electronic trip mechanisms in UL489 devices, ensuring precise and timely interruption of fault currents. These technologies promote energy efficiency and stability within electrical systems. In addition, many of these devices are equipped with indication features, providing clear visual status cues for quick assessment in emergency situations.

In terms of characteristics, both UL1066 and UL489 devices adhere to rigorous testing and certification processes to meet UL standards. This compliance assures users of their performance and reliability. Furthermore, the devices are designed to accommodate a wide range of operating temperatures and environmental conditions, making them versatile choices for various applications.

In summary, Siemens UL1066 and UL489 devices are paramount in ensuring safety and efficiency in electrical circuits. Their advanced features and robust construction make them indispensable in protecting both personnel and equipment in an array of industrial and commercial applications.