Siemens UL1066, UL 489 specifications 81THDC

Models: UL 489 UL1066

1 92
Download 92 pages 35.36 Kb
Page 28
Image 28

Communication-capable Circuit Breakers

WL Circuit Breaker

The extended protective relay functions of the metering function can monitor the following criteria and initiate a trip if values are exceeded.

Protective Relay Function

ANSI Device Number

Setting range

Possible delay

Current unbalance

46

5 ...

50%

0 ...

15 s

Total harmonic distortion - current

81THDC

5 ...

50%

5 ...

15 s

 

 

 

 

 

 

Voltage unbalance

47

5 ...

50%

0 ...

15 s

 

 

 

 

 

 

Undervoltage

27

100

... 1100V

0 ...

15 s

 

 

 

 

 

 

Overvoltage

59

200

... 1200V

0 ...

15 s

Total harmonic distortion - voltage

81THDV

5 ...

50%

5 ...

15 s

 

 

 

 

 

 

Direction of phase rotation

47N

-

 

-

 

 

 

 

 

 

 

Active power in normal direction

32

13 ...

4000kW

0 ...

15 s

 

 

 

 

 

 

Active power in reverse direction

32R

13 ...

4000kW

0 ...

15 s

Under frequency

81U

40 ...

70 Hz

0 ...

15 s

 

 

 

 

 

 

Over frequency

81O

40 ...

70 Hz

0 ...

15 s

Table 2-8Additional trip criteria can be set using the extended protective relay functions. A delay time can be set to prevent transient events from causing nuisance trips: the circuit breaker will not trip unless the condition is present for longer than the delay time.

The metering function supplies the following Alarm Setpoint Functions:

Alarm Function

Setting range

Possible delay

Over current

30 ...

10000A

0 ...

255 s

Over current - ground fault

30 ...

10000A

0 ...

255 s

Over current - N-conductor

30 ...

10000A

0 ...

255 s

 

 

 

 

 

Phase unbalance - current

5 ...

50%

0 ...

255 s

Demand - current

30 ...

10000A

0 ...

255 s

Total harmonic distortion - current

5 ...

50%

5 ...

255 s

Undervoltage

15 ...

1200V

0 ...

255 s

Overvoltage

200

... 1200V

0 ...

255 s

Phase unbalance - voltage

5 ...

50%

0 ...

255 s

Total harmonic distortion - voltage

5 ...

50%

5 ...

255 s

Crest factor

1 ...

3,000

0 ...

255 s

Form factor

1 ...

3,000

0 ...

255 s

 

 

 

 

 

Active power in normal direction

13 ...

10000kW

0 ...

255 s

Active power in reverse direction

13 ...

10000kW

0 ...

255 s

Leading power factor

0 ...

-0.99

0 ...

255 s

 

 

 

 

 

Lagging power factor

0 ...

0.99

0 ...

255 s

 

 

 

 

Demand - active power

-10000 10000kW...

0 ...

255 s

 

 

 

 

 

Apparent power

13 ...

10000kVA

0 ...

255 s

 

 

 

 

 

Reactive power in normal direction

13 ...

10000kvar

0 ...

255 s

 

 

 

 

 

Reactive power in reverse direction

13 ...

10000kvar

0 ...

255 s

 

 

 

 

 

Demand - apparent power

13 ...

10000kVA

0 ...

255 s

 

 

 

 

 

Demand - reactive power

13 ...

10000kvar

0 ...

255 s

 

 

 

 

 

Underfrequency

40 ...

70 Hz

0 ...

255 s

 

 

 

 

 

Overfrequency

40 ...

70 Hz

0 ...

255 s

Table 2-9Alarm and setpoint functions allow events to be generated when system conditions deviate from their nominal values. The generation of the events can be delayed to prevent transient conditions from “chattering”. These alarms are communicated via CubicleBUS and can cause output contacts to close in the configurable output module and can freeze the waveform buffer in the metering function. Alarms are communicated to the COM16/15 where they can be transmitted to the master.

2/17

WL MODBUS Communication and Electronic Accessories • January 2005

Page 28
Image 28
Siemens UL1066, UL 489 specifications 81THDC