4.OPERATION

4.1 Introduction

Under normal conditions the sensor module does not require operator or technician intervention. The fol- lowing are conditions under which the module requires attention:

-Routine periodic calibration.

-Calibration after a high gas alarm.

-Sensor replacement on a planned schedule or when a sensor failure occurs.

-Periodic cleaning as necessary.

-Unanticipated maintenance.

4.2Signal Value

During normal operation the current loop of the sen- sor module and the controller will be between 4 mA indicating no presence of gas, and 20 mA indicating that the full scale concentration of gas is present. The signal value is proportional to the concentration of gas present.

FAULT /KEYPAD

MODEL 4105-02

Combustibles % LEL

Unity

SPAN

ZERO

 

 

 

Ph. 408-262-6611

Milpitas, CA

CAL

FAULT /KEYPAD

MODEL 4105-05

H2S PPM

Unity

SPAN

ZERO

 

 

 

Ph. 408-262-6611

Milpitas, CA

CAL