6.4a. Combustibles
1.Verify the voltage across A to R equals 2 volt. If not, adjust volts potentiometer R11
2.Verify the voltage from GND (TB2) to VOUT equals 0.4 volts. If not adjust BAL potentiom- eter (R2)
3.Verify that the voltage at VOUT is equal to the voltage desired.
•The VOUT test point on the I/O PCB has a range of
•Selecting the jumper at JP1 assigns one of four different sensitivity ranges to the module. The JP1 positions are labeled 1, 2, 3 & 4. JP1 jumper set the coarse up scale SPAN values by affect- ing the gain of the analog circuit. JP1 is set correctly if an application of 50% of full scale reads between 1.0 & 1.4 volts on VOUT. Fine- tuning of these setting is done later by adjust- ing the
JP1 gain values are as follows:
JP1 with jumper in position 1 = GAIN = 51 JP1 with jumper in position 2 = GAIN = 26 JP1 with jumper in position 3 = GAIN = 12.5 JP1 with jumper in position 4 = GAIN = 7 JP1 with no jumper = GAIN = 1
•More than one jumper may be installed to allow additional gain value. Multiple jumper are addi- tive in relation of the gain value. For example, if a gain of 20 is needed, jumper should be placed in positions 3 and 4 to provide a gain of 20.
6.4b LEL Sensor Fault Supervision
The typical failure mode of catalytic bead sensors is the reference or active beads open circuit. In rare cases a short circuit may develop. The 4105- 02 is equipped with fault detection circuitry that detects either condition. A FAULT is also signaled if the output drifts below
6.4c Electrochemical (Oxygen and Toxics)
Verify that the voltage VOUT is equal to the volt- age as desired.
•The VOUT test point on the I/O PCB has a range of
Model 4105 Gas Sensor Module (12/02)
Instruction Manual
•The
•The JP1 positions are labeled 1, 2, 3 & 4.
•JP1 jumper set the coarse up scale SPAN values by affecting the gain of the analog circuit.
•JP1 is set correctly if a 50% of
•
•Select the jumper at JP1 as required. JP1 gain values are as follows:
JP1 with jumper in position 1 = GAIN = 5.5 JP1 with jumper in position 2 = GAIN = 4 JP1 with jumper in position 3 = GAIN = 2.3 JP1 with jumper in position 4 = GAIN = 1.5 JP1 with no jumper = GAIN = 1
•More than one jumper may be installed to allow additional gain value. Multiple jumper are addi- tive in relation of the gain value. For example, if a gain of 6.5 is needed, jumper should be placed in positions 2 and 3 to provide a gain of 6.3.
Note: Allow the new sensor to stabilize for a mini- mum of 30 minutes and then calibrate using the procedure in Section 5.
6.4d Missing Electromechanical Sensor Fault Supervision
Many electromechanical sensor housings allow for easy replacement of defective sensors by making the sensors 'plug in'. A problem is that if the sensor is removed, many transmitters continure to display the safe reading of 0 PPM. The
Page: 7