3. INSTALLATION
NOTE
All IT modules are factory are
All modules are tagged to indicate the configuration including the sensor module number.
Identify all components during unpacking and install using the factory configuration.
3.1SENSOR MODULE LOCATIONS
Select locations for each sensor modules based on the following:
•Modules should be placed close to the potential source of gas.
•Modules should be placed in areas accessible for calibration.
•Sensors should be pointed down and the conduit should include an inverse trap to reduce moisture (condensation) from accumulating in the electronics enclosure.
•Remote calibration fitting
3.2WIRING
3.2.1ANALOG
The
3.2.2MODBUS OPERATION USING RS-485 CONNECTION
Use a minimum of 18 AWG, 2 conductor for DC power connection. No shield required. In addition use a minimum of 24 AWG, low capacitance, shielded data cable for
Refer to Figure
3.2.3SENTRY OPERATION USING SMC SENTRY CONNECTION
Wire shall be rated as 600 volt tray cable, such as Belden (or equivalent) 27331 or 27331 AS (shielded). If high RFI or EMI levels exist wiring should be protected by conduit or shield. The installation may be planned in a manner which provides up to 4 sensor modules on a single home run to a Sentry controller.
NOTE:
Be sure to follow all local electric code and safety requirements when installing the
3.2.4 GENERAL
Install conduit as required by local code or construction specifications. When sensor modules are to be multiplexed for Sentry or
•Install splice boxes above each sensor module. Use
Page: 7