PCB Label

6.Carefully return the transmitter to the enclosure installing it over the two stand-off’s. Tighten the retaining screws into the stand-offs.

P1

PCB Label

 

Function

1

Switch

 

IN +

Digital Input SW +

2

 

 

IN -

Digital Input SW -

3

4-20

 

IN +

4-20 mA Input +

4

 

 

IN -

4-20 mA Input -

5

GND

 

 

Ground

6

4-20

 

OUT +

4-20 mA Output +

7

 

 

OUT -

4-20 mA Output -

P2

PCB Label

 

Function

1

RS 485

 

+

RS 485 (+) (A)

2

 

-

RS 485 (-) (B)

3

 

 

S

RS 485 shield (Isolated GND)

4

RS 485

 

+

RS 485 (+) (A)

5

 

-

RS 485 (-) (B)

6

 

 

S

RS 485 shield (Isolated GND)

P3B

PCB Label

Function

1

P

Power

2

S

Signal

3

G

Ground

P3A

 

 

4

5

6

P

Power

S

Signal

G

Ground

P4 Connections are only available when the optional Relays are included

P4

PCB Label

 

 

Function

1

LO ALM

N/C

Low

Alarm Relay NC

2

COM

Low Alarm Relay COM

3

 

N/O

Low Alarm Relay NO

4

HI ALM

N/C

High Alarm Relay NC

5

COM

High Alarm Relay COM

6

 

N/O

High Alarm Relay NO

7

TRBL

N/C

Trouble Alarm Relay NC *

8

COM

Trouble Alarm Relay COM*

9

ALM

N/O

Trouble Alarm Relay NO*

*Trouble relay is fail safe so it is energized for normal operation, functions are labeled for normal operation.

Table 3-1

Sensor Module External Interfaces (See Figure 3-2)

7. Establish the module address according to section 3.5.

NOTE

The starting delay period normally takes approximately 3 minutes but under some

circumstances can take longer.