3.5 MODULE ADDRESS SWITCH

3.5 MODULE ADDRESS SWITCH

For digital interface applications the module address switch (or Modbus node) must be set per Table 3-2:

 

POSITION

ADDRESS

POSITION

 

ADDRESS

 

 

1

Sensor 1

9

 

Sensor 09

 

 

2

Sensor 2

A

 

Sensor 10

 

 

3

Sensor 3

B

 

Sensor 11

 

 

4

Sensor 4

C

 

Sensor 12

 

 

5

Sensor 5

D

 

Sensor 13

 

 

6

Sensor 6

E

 

Sensor 14

 

 

7

Sensor 7

F

 

Sensor 15

 

 

8

Sensor 8

0

 

Software

 

 

 

 

 

 

Menu

 

Table 3-2

Sensor Module Address Switch Positions

NOTE

For Sentry applications only sensor addresses 1-8 are allowed. If using Modbus output sensor addresses 1-15 are available. Position 0 allows the Modbus Address to be set by software menu, in the range 16-254.