G. ALARM Indicator Audible alarms will sound off if any of the following conditions occur:

a)OVERTEMP condition

b)

Low Battery Voltage

:

<10.7V

c)

Low Volt. Shutdown

:

<10.0V

6.2 Operating Limits

A. Power Output

The Sima STP-3000 delivers 2500 watts or 22.7 amperes continuously and about 3000 watts or 27.3 amperes for approximately 5 minutes. The Sima STP-3000 must be cooled down for minimum 15 minutes before it resumes operation at 2500 / 3000 watts. Wattage rating is for resistive loads like heaters while current rating is for reactive loads like motors.

It operates most AC loads within these ratings and will normally start single-phase induction motors rated at 1HP or less. It fails to start large inductive motors due to huge starting currents.

If the battery voltage indicator drops below 11 volts when the Sima STP-3000 is attempting to start a motor, it would not start. Ensure proper battery connections and being fully charged. Larger batteries may be needed if voltage still drops below 11 volts. See battery-sizing notes in Appendix A.

B. Input Voltage

The STP-3000 operates with input voltage between 10 ~15-volts. Its optimum performance ranges with input voltage between 12.0- and 14.0-volts. Low battery warning will sound with the voltage indicator in the lower red zone when input voltage drops below 10.7 volts. Voltage below 10 volts shall shut down the inverter in order to protect your batteries from being over-discharged. It takes an input voltage above 11-volts to restart the STP-3000 inverter.

Input voltage above 15-volts also shuts down the inverter so as to protect the unit from excessive input voltage. The voltage indicator will be in the upper red zone. Avoid input voltages exceeding 16-volts as it may damage the inverter permanently.

7. Accessories

7.1 AC Receptacle option

The AC receptacle on front panel of the Sima STP-3000 inverter offers ready access to AC power for outputs limited to 1500 watts (15A) per outlet.

7.2 Remote ON/OFF switch option

This option allows the Sima STP-3000 inverter be turned on and off from a remote switch positioned up to 20 feet (6.1 meters) away, with push-button and indicator light showing inverter status (See your SIMA dealer for more details on the STP-3000 Remote ON/OFF switch).

7.3 DC Box-Lug connectors

Available at electrical parts suppliers, box-lug connectors may be used in place of ring terminals.

7.4 Manual or Automatic Transfer Switch

To select between power sources from inverter, generator or utility power, use manual or automatic transfer switches. The double-pole, double-throw (DPDT) switch breaks the load from one power source before making connections to another (See Section 5.2). Transfer switch is available from marine and RV equipment dealers. Purchase only agency-approved switch that covers both ratings of the inverter and the other power source

7.4 Maintenance

Your Sima STP-3000 requires very little maintenance. Clean the exterior periodically with a damp cloth to prevent accumulation of dust and dirt, especially for the air intake on the rear panel and exhaust slots on the front panel to remove accumulation of dust and dirt. Regular maintenance check is recommended. Tighten screws on the DC input terminals periodically.

8. Troubleshooting

8.1Common Problems A. Buzz in Audio Systems

Portable stereo systems may not adequately filter the modified sine wave, thus producing buzzing noise from their loudspeakers when powered by Sima STP-3000 inverter. Sound systems with higher quality power supplies are recommended.

B. Television Interference

Television reception may be interfered when operating the Sima STP-3000inverter. Observe the following steps to alleviate the problem:

1Secure the chassis ground lug on the rear panel of the Sima STP-3000solidly to the ground system of your vehicle, boat and home.

2Do not operate high power loads simultaneously while watching television.

3Ensure the antenna feeding the television set with adequate (“snow free”) signal and that good quality cable feeding the television.

4Keep a distance between the televisions from the Sima STP-3000inverter.

5Minimize the cable length between the battery and the Sima STP-3000with twists so as to minimize the radiated interference from the cables.