Poor COOL(HEAT) operation

Improper set of temperature Adjust set temperature

If cooling (heating) load is Check the forecasted load of cooling (heating) proper

 

 

 

 

 

 

 

 

 

 

 

 

 

heck and fill the leakage, then

 

 

 

 

 

 

The refrigerant has leakage or is

 

 

 

 

 

 

 

vacuumize it and supplement the re-

 

 

 

 

 

 

 

insufficient

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

frigerant as required

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Leakage between the high pres-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the compressor

 

 

 

 

 

 

sure and the low pressure in-

 

 

 

 

 

Malfunction of

 

 

 

 

 

 

 

 

 

 

 

side the compressor

 

 

 

 

 

 

 

 

r e f r i g e r a n t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

flow

 

 

 

Malfunction of four-way valve

 

 

 

Replace the four-way valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Local block of capillary

 

 

 

Replace the capillary

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Judge whether the system is blocked by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

observing the condensation of evapora-

 

 

 

 

 

 

Blockage of cooling system

 

 

 

 

 

 

 

 

 

 

 

tor and the pressure value of the high

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure manometer and take measures

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to deal with the system.

 

 

Heat insulation for the connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Make sure that heat insulation for the thick and thin pipes

 

pipes of the indoor unit and the out-

 

 

 

 

 

 

 

is good. Heat insulation must also be provided for the

 

 

 

 

 

door unit is bad.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

joint andthe exposed part of the copper pipe .

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air circulation is insufficient

 

Block of outdoor heat ex-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Clean the dust accumulated on the surface of

 

 

 

 

 

 

 

 

 

changer

 

 

 

 

 

 

the heat exchanger.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Clean the filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air filter were blocked

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To set the fan speed to high or

 

 

 

 

Fan speed was set too slow

 

 

 

 

 

 

 

middle speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace the capaci-

 

 

 

 

 

 

 

 

 

 

 

Capacitor

 

 

 

Fan rotation speed becomes

 

 

 

 

damage

 

 

tor

 

 

 

low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor damage

 

 

 

Replace the motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The installation position of the

 

 

 

 

 

 

Good ventilation must be provided for the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outdoor unit is not appropriate.

 

 

 

 

 

installation position of the outdoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Properly install the rainproof plate or the sunproof plate. If the

The outdoor temperature is too high.

 

 

 

 

 

 

maximum cool air still can not meet the requirement, it is sug-

 

 

 

 

 

 

 

 

gested to replace the air conditioner.

 

 

 

 

 

 

 

 

 

 

The air tightness is not enough. People

 

 

 

Keep certain air tightness indoors, try not to use

come in and out too frequently. There

 

 

 

 

 

 

electricalappliance with large quantity of heat

are heating devices indoors.

 

 

 

 

 

 

 

 

 

 

 

 