DRY Modes

When Tamb.Tpreset2 , the unit will run under DRY cooling mode, in which case the compressor and outdoor fan will be started and the indoor fan will run at low speed.

When Tpreset 2 Tamb.Tpreset 2 , the unit will run under Dry mode, in which case the indoor fan will keep run at low speed, the compressor and outdoor fan will be stopped after 6mins. After 4 minutes, the compressor and outdoor fan will be restarted. The dehumidifying process is so repeated in cycle.

When Tamb.Tpreset 2, the compressor and outdoor fan will be stopped, the indoor fan will run at low speed. Under this mode, the switchover valve will not be powered on and the setting temperature range is 16-30.

Tamb.

 

 

 

Start cooling

Tpreset

 

 

 

 

 

 

 

 

Dehumidifying

Tpreset

 

 

 

 

min.

min.

min.

min.

Stop running

 

 

 

Compressor

Outdoor fan

Indoor fan

Preset speed

RunStop

Protection

Antifreeze Protection

Under dehumidifying and cooling mode, i f it is detected that the system is under antifreeze protection, the compressor and and outdoor fan will be stopped, and the indoor fan will run at low speed. When antifreeze protection is released and the the compressor has stoppedfor 3 minutes, the complete unit will resume its original operating status.

Upon meeting "run 6 mins and stop 4 mins" dehumidify condition, if it is detected that the system is under antifreeze protection,the compressor and outdoor fan will be stopped, and the indoor fan will run at low speed. When antifreeze prote-

Other protection ction is released and the compressor has stopped for 4 minutes, the complete unit will resume its original operating status.

The other protections are the same with that under Cool mode.

HEAT Mode (there is no this mode for cooling only unit)

The conditions and process of heating

When Tamb Tset 2 ,the system enters heating running, in this case, the reversal valve, compressor, outer fan enter simultaneously running.The indoor fan will delay at most for 2min to run.

When Tamb Tset 4 ,the compressor and outdoor fan will stop, but the reversal valve is still with power on, the indoor unit will run at setting fan speed for 60s then will stop .

When Tset2TambTset 4 ,the unit will maintain its original operating status.

Under this mode, the switchover valve will be powered on and the setting temperature range is 16-30 .

Tpreset

 

 

Stop heating

 

 

 

 

 

 

Original running state

Tpreset

 

 

 

Tamb.

 

 

Start heating

 

 

 

6Min.

3Min.

 

6Min.

Compressor

 

 

 

Outer fan

 

 

 

Inner fan 2Min.

Setting

2Min.

Setting

fan speed

fan speed

 

 

Inner fan

 

 

 

Running

 

 

Stop

Conditions and processes of defrost

This unit adopt intelligent defrosting,it can defrost according to the frosting conditions,dual 8 display H1

Protection

Anti-high temperature protection

Page 15
Image 15
Sinclair ASH-09AK, ASH-13AK service manual RunStop

ASH-09AK, ASH-13AK specifications

The Sinclair ASH-13AK and ASH-09AK are two remarkable electric aircraft developed by Sinclair Aeronautics, exemplifying cutting-edge technologies and contemporary design philosophies within the realm of aviation. Both models are designed to meet the growing demand for eco-friendly flight solutions, paramount in contemporary aviation discussions focused on sustainability and efficiency.

The ASH-13AK is a sleek glider that emphasizes aerodynamic efficiency. It features a wingspan of 13 meters, designed with advanced composite materials that contribute to its lightweight structure while ensuring robustness. The aerodynamic design allows for excellent lift-to-drag ratios, making it highly efficient in its operational capabilities. With its innovative control surfaces, the ASH-13AK enhances maneuverability, enabling pilots to experience heightened responsiveness during flight.

On the other hand, the ASH-09AK, a slightly smaller variant with a wingspan of 9 meters, focuses on agility and versatility. This model is particularly suited for training environments and leisure flying, offering novice pilots an accessible entry into the world of gliding. The ASH-09AK also incorporates state-of-the-art avionics, ensuring that pilots have access to modern navigation and real-time data during their flights.

Both aircraft integrate advanced battery technologies that provide extended flight times and reduce reliance on ground support. The electric propulsion systems utilized by the ASH-13AK and ASH-09AK allow for quieter operation and zero emissions during flight. This not only minimizes the environmental footprint but also enhances the flying experience by allowing for serene, unobtrusive navigation across the skies.

The intuitive cockpit design in both models includes user-friendly interfaces that display critical flight information, making piloting more accessible even for those less experienced. The ergonomic seating and cockpit layout ensure comfort during extended flights, with ample visibility for the pilot to navigate seamlessly.

In summary, the Sinclair ASH-13AK and ASH-09AK are exemplary electric aircraft that showcase modern engineering prowess. Their focus on sustainability, efficiency, and user-friendly technologies demonstrate Sinclair Aeronautics' commitment to advancing the future of aviation, making them noteworthy additions to the electric aircraft market. With continued innovation and development, both models are set to inspire a new generation of aviators seeking eco-conscious flying experiences.