Image 11

Tpreset +2Tamb

 

 

Cooling

 

 

 

 

 

 

Dry

Tpreset -2

6 min.

6 min.

Stop

 

 

 

4 min.

4 min.

Compressor

 

 

 

Outdoor fan

 

 

 

Indoor fan

low speed

 

 

Run

 

Stop

6.1.2.2.3 Protection

Antifreeze Protection

Upon meeting the cooling condition, if it is detected that the system is under antifreeze protection, the compressor and outdoor fan will be stopped,and the indoor fan will run at low speed. When antifreeze protection is released and

the compressor has stopped for 3 minutes, the complete unit will resume its original operating status.

Upon meeting the dehumidify condition, if it is detected that the system is under antifreeze protection, the com

-pressor and outdoor fan will be stopped,and the indoor fan will run at low speed. When antifreeze protection is released and the compressor has stopped for 4 minutes, the complete unit will resume its original operating status.

6.1.2.3HEAT Mode (there is no this mode for cooling only unit)

6.1.2.3.1The conditions and process of heating

When Tamb Tset +2 ,the system enters heating running, in this case, the reversal valve, compressor, outer fan enter simultaneously running.The indoor fan will delay at most for 2min to run.

When Tamb Tset +4,the compressor and outdoor fan will stop, but the reversal valve is still with power on, the indoor unit will run at setting fan speed for 60s then will stop .

When Tset +2 <Tamb < Tset +4 ,the unit will maintain its original operating status.

Under this mode, the switchover valve will be powered on, and the setting temperature range is16 ~30 .

 

 

 

 

Stop heating

Tset

 

 

 

 

 

 

 

 

Original running state

Tset

 

 

 

 

 

Tamb.

 

 

Start heating

 

6Min.

3Min.

6Min.

 

Compressor

 

 

 

 

Outer fan

 

 

 

 

Inner fan

2Min.

Setting

2Min.

Setting

fan speed

fan speed

 

 

 

Reversal valve

 

 

 

 

6.1.2.3.3 Conditions and processes of defrost

Running

Stop

This unit adopt intelligent defrosting,it can defrost according to the frosting conditions,dual 8 display H1

6.1.2.3.4 Protection

High Temp. Protection

If it is detected that the evaporator tube temperature is too high, the outdoor fan will be stopped. When the tube temperature resumes to normal, the outdoor fan will be restarted.

Noise Silencing Protection: If the unit is stopped by pressing ON/OFF, the reversal valve will be stopped after

2-minute lag; or 2 minutes will be delayed upon mode switching.

6.1.2.4 Fan mode

Under FAN mode, only the indoor fan runs at setting speed.The RUN indicator will be bright. Double 8 module indicator will display the setting temperature. When stand by, the power indicator is bright but the unit does not run.

6.1.2.5 Auto Mode

Under this mode, the system will automatically select its run mode (cool, dehumidify, heat or fan) with the change of ambient temperature. For protection function, same as under cooling and heating mode.