Sinclair ASH-13AK, ASH-09AK service manual Manual 2 of functions of remote controller

Models: ASH-09AK ASH-13AK

1 49
Download 49 pages 2.17 Kb
Page 14
Image 14

Manual 2 of functions of remote controller

This manual is applicable to 18K, 24K models, the centigrade is used for the following function manual, if there will be the Fahrenheit degree, that will be TF= TCX1.8+32.

1. Temperature parameter

The room setting temperature(Tpreset)

The room ambient temperature (Tamb)

Basic Functions

Once energized, the compressor should in no way be restarted unless after 3-minute time interval at least for the first energization, the compressor will be started without 3-minute lag. The compressor, once started, will not be stopped within 6 minutes with the charge of room temperature.

Cooling Mode

Cooling Conditions and Process

When Tamb.Tpreset 1 , the unit will run under cooling mode, in which case the compressor and outdoor fan will start and the indoor fan will run at setting speed.

When Tamb. Tpreset 1, the compressor and the outdoor fan will stop, the indoor fan will run at setting speed. When Tpreset 1 Tamb. Tpreset 1, the unit will maintain its original operating status.

Under this mode, the four-way valve will not be powered on and the setting temperature range is 16-30. The displayer displays running signal, cooling signal and setting temperature.

amb.

 

Start cooling

Preset

 

Original operating status

 

 

Preset

 

Stop cooling

 

 

min.

min.

min.

Compressor

 

 

Outdoor fan

 

 

Indoor fan

Preset speed

 

Run

 

Stop

Protection

Antifreeze Protection

If it is detected that the system is under antifreeze protection, the compressor and outdoor fan will be stopped, and the indoor fan will run at setting speed. When antifreeze protection is released and the compressor has stopped for 3 minutes, the unit will resume its original operating status.

 

During antifreeze protection

Compressor

3 min.

Outdoor fan

 

Indoor fan

Preset speed

Run

Stop

Over current protection

If it is detected that the system amperage exceeds the specified value(about 22 A), the main unit will enter into the status that only the fan is running. After 3 minutes and overcurrent protection is released, the main unit will resume its original operating status .If it is 6 times continuously detected overcurrent protection (if the compressor has run over 6 mins continuously, the times of protection will be cleared),the main unit will be stopped on standby,the nixietube will display error code "E5", power indicator will blink and it is need to restart the unit by the wireless remote control.

DRY Modes

Page 14
Image 14
Sinclair ASH-13AK, ASH-09AK service manual Manual 2 of functions of remote controller