INTREPID

BURNER DATA – BECKETT CF-375 BURNERS FOR PACKAGED BOILERS ONLY

(For knocked-down & boiler burner units see publication no. TR-42KB)

 

 

 

Nozzles

 

 

 

 

 

Boiler

Burner

Firing Rate

Size

Angle &

 

Oil Pump Pressure

Air Shutter

Air Band

Head

Model

Model *

(GPH)

(GPH)

Type

MFG

Setting (PSIG)

Setting

Setting

Setting

TR-60

CF-375

2.60

2.25

45˚ P

HAGO

135

10

3

1

TR-60

CF-375

2.85

2.25

45˚ P

HAGO

160

10

2

2

TR-70

CF-375

3.00

2.5

45˚ SS

HAGO

145

10

4

3

TR-70

CF-375

3.10

2.5

45˚ SS

HAGO

155

10

4

4

TR-70

CF-375

3.35

2.75

45˚ B

DELEVAN

148

10

4

5

 

 

 

 

 

 

 

 

 

 

Air shutter and air band settings shown are approximate ONLY. See START-UP page 8.