Console Specifications
CS – 0206VLII
4/4/2006
Page 2 of 7
a. Full Access (front and rear) where ever possible to
house terminals and CPUs
b. Air circulation throughout the entire installation
c. Fully removable rear doors and front panels requiring
no tools
d. Monitor mounts are adjustable to enhance viewing
angle
e. Cable Management run flexibility
f. Unparalleled strength and durability for 24/7
operations.
1.5 Doors and Access –
Front access panels are constructed of 20 Ga. cold rolled steel, providing
durability and strength. Rear Doors and hinged to allow access to cable
management within frame. With the exception of the work surface top,
rear doors, and trim pieces, the entire unit is made of steel.
1.6 Work Surface –
The console shall have a minimum 1.25" (50mm) thick work surface with
post-formed front edge, T-Mold or specific edging for operator comfort can
be supplied. Work surfaces are constructed of high-pressure post-formed
grade laminate applied to .45 lb. industrial grade board for durability. A
thermal fused melamine backer is applied to seal the board and eliminate
rough surfaces on the underside of the work surface and to prevent
moisture access to the work surface.
2) Standards
2.1 Optional rack mount insert shall comply with Electronic Industry
Association (E.I.A.) specifications for rack mounting ANSI/EIA standard
RS-310.
2.2 The consoles shall be manufactured to industry recognized quality and
ergonomic standards (BIFMA, ISO, ANSI).
3) Drawings
3.1 The contractor shall supply sets of scaled drawings for each console
assembly showing the location of all the specified electronics in isometric
view in addition to a plan (top down) and elevation views.
3.2 The specification of sizes and dimensions shown in the drawings shall
have a tolerance of not more than +/- 0.062" (1.6mm).