Page 4 | SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS |
All Air From Inside The Building
If the boiler is to be located in a confined space minimum clearances of 24 in, 610 mm must be maintained between the boiler and any adjacent construction. When installed in a confined space, two permanent openings communicating with an additional room(s) are required. The combined volume of these spaces must have sufficient volume to meet the criteria for an unconfined space. The total air requirements of all fuel burning equipment or any type of exhaust fan must be considered when making this determination.
Each opening must have a minimum free area of 1 in2/ 1000 Btu/hr, 140 in2/GPH, 2200 mm2/kW based on the total input rating of ALL fuel burning equipment in the confined area. Each opening must be no less than 100 in2, 64,516 mm2 in size. The upper opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the top of the enclosure.
The bottom opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the bottom of the enclosure.
All Air From Outside The Building
When installed in a confined space Two permanent openings communicating directly with, or by ducts to, the outdoors or spaces that freely communicate with the outdoors must be present. The upper opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the top of the enclosure. The bottom opening must be within 12 in, 305 mm of, but not less than 3 in, 76 mm from, the bottom of the enclosure.
Where directly communicating with the outdoors or communicating with the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in2/ 4000 Btu/hr, 35 in2/GPH, 550 mm2/kW of the total input rating of all of the equipment in the enclosure.
Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 in2/2000 Btu/hr, 70 in2/GPH, 1100 mm2/ kW of the total input rating of all of the equipment in the enclosure. When ducts are used, they must have the same
Table 1-
Required Cross Sectional Area (in2)
|
| Metal | Wooden |
Input | 1/4" Wire | Louvers | Louvers |
(MBH) | Screen | 75% Free Area | 25% Free Area |
1000 | 250 | 333 | 1000 |
1200 | 300 | 400 | 1200 |
1400 | 350 | 467 | 1400 |
1600 | 400 | 533 | 1600 |
1800 | 450 | 600 | 1800 |
2000 | 500 | 667 | 2000 |
2200 | 550 | 733 | 2200 |
2400 | 600 | 800 | 2400 |
2600 | 650 | 867 | 2600 |
2800 | 700 | 934 | 2800 |
3000 | 750 | 1000 | 3000 |
3200 | 800 | 1066 | 3200 |
3400 | 850 | 1134 | 3400 |
3600 | 900 | 1200 | 3600 |
3800 | 950 | 1267 | 3800 |
4000 | 1000 | 1334 | 4000 |
4200 | 1050 | 1400 | 4200 |
4400 | 1100 | 1467 | 4400 |
4600 | 1150 | 1533 | 4600 |
4800 | 1200 | 1600 | 4800 |
CHIMNEY & VENT PIPE
CONNECTIONS
WARNING: The vent installation must be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1/ NFPA
CAUTION: The products of combustion from a 28A must be safely vented to the outdoors while ensuring that the flue gasses do not cool prematurely. It’s critical that the chimney system be properly designed to handle the flue gases. An oversized or uninsulated chimney can cause the moisture in the flue gases to condense resulting in damage to the chimney system unless it’s specifically designed for condensate. If this is the case a suitable condensate drain must be used to protect the boiler from condensate.
NOTE: Our warranty does not cover corrosion damage to the boiler or its vent system caused by flue gas condensate!