Soleus Air KFTHP-24-OD, 3119233 1Installation Instructions, Outdoor Unit, Wire Gauge Requirements

Models: 3119233 KFTHP-24-ID KFTHP-24-OD KFTHP-18-ID KFTHP-12-ID KFTHP-12-OD KFTHP-18-OD

1 26
Download 26 pages 4.14 Kb
Page 18
Image 18
 Outdoor Unit

1Installation Instructions

4. Connecting of the Cable

Wire Gauge Requirements Indoor Unit

Connect the power connecting cord to the indoor unit by connecting the wires to the terminals on the control board individually in accordance with the outdoor unit connection.

Note: For some models, it is necessary to remove the cabinet to connect to indoor unit terminal.

Manual background Outdoor Unit

1). Remove the access door from the unit by loosening the screw. Connect the wires to the terminals on the control board individually as the following.

2). Secure the power connecting cord onto the control board with cable clamp.

3). Reinstall the access door to the original position with the screw.

4)Use a recognized circuit breaker for 24K.30K model between the power source and the unit. A disconnecting device to adequately disconnect all supply lines must be fitted.

Front panel

Terminal (inside)

Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background Cabinet

Indoor unit

Chassis

Access door

Terminal(inside)

Outdoor unit

The figures in this manual are based on the external view of a standard model. Consequently, the shape may differ from that of the air conditioner you have selected.

Caution:

1.Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, refer to the circuit diagram posted on the inside of the access door .

2.Comfirm that the cable thickness is as specified in the power source specification. (See the cable specification table below)

3.Check the wires and make sure that they are all tightly fastened after cable connection.

4.Be sure to install an earth leakage circuit breaker in wet or moist area.

Wire Gauge Requirements

Circuit

Amp

15

20

25

30

35

40

45

50

200ft

6

4

4

4

3

3

2

2

Wire Gauge at Different Wire Lengths

150ft100ft

810

68

68

46

46

46

34

34

50ft

14

12

10

10

8

8

6

6

(Nec,105c/221 F Type Copper Conductors)

16

Page 18
Image 18
Soleus Air KFTHP-24-OD, KFTHP-18-OD, KFTHP-12-OD, 3119233 1Installation Instructions, Outdoor Unit, Wire Gauge Requirements