Marley / Sigma 1000/1200 CoolingTower / Specifications: Base
Specifications | Specification Value |
3.0Construction:
16
3.1 | The tower shall be capable of with- | ■The limiting water quality values indicated are those which are |
| standing water having a pH of 6.5 to | acceptable for the normal materials of construction specified. If |
| 8.0; a chloride content (NaCl) up to 750 | water of more aggressive quality is anticipated please change |
| ppm; a sulfate content (SO4 ) up to | hardware material requirement to 300 Series stainless steel, as |
| 1200 ppm; a sodium bicarbonate con- | indicated below and following. |
| tent (NaHCO3) up to 200 ppm; a cal- |
|
| cium content (CaCO3) up to 800 ppm; |
|
| silica (SiO2) up to 150 ppm; and design |
|
| hot water temperatures up to 120°F. |
|
| The circulating water will contain no |
|
| oil, grease, fatty acids, or organic sol- |
|
| vents. |
|
3.2The structural framework of the tower shall be Douglas Fir, designed in accor- dance with CTI
3.3All wood components shall be treated
| after fabrication with chromated cop- | Cooling Technology Institute standards take into account the hot, |
| per arsenate (CCA) by the | humid environment in which a cooling tower normally operates. |
| process to a chemical retention of 0.4 | This environment can render the limits of customary construction |
| lbs/ft3. | standards inadequate for cooling tower design. |
3.4 | Structural columns and diagonals shall | The importance of shear plates is discussed at length in |
| be 4"x4". Framing girts may be 2"x4", | Marley Difference, “Item |
| except for those supporting the hot | a copy. |
| water basins and fill. Those girts shall | See notes on page 27 regarding the use and availability of red- |
| be 2"x6" minimum, located both sides | |
| of the support columns. | wood. |
3.5 | Multicell towers shall include treated | Specification of minimum member sizes assures that all offerings |
| Douglas Fir plywood partitions | will conform to an industrial level of construction. |
| between cells in the plenum area. | Multicell towers must have plenum partitions between cells. |
| Partitions shall extend the full height of | |
| the tower from the base of fill to the | Otherwise, air will be induced downward through an inoperative |
| underneath side of the fan deck. | fan, bypassing the fill entirely. Without these partitions, |
|
| or |
3.6 | Column lines shall be on no greater | isfactory. |
| than |
|
| the base of all perimeter columns |
|
| shall be firmly anchored to galvanized |
|
| steel base plates. Framing joints shall |
|
| be made with 1/2" diameter or larger |
|
| series 300 stainless steel machine |
|
| bolts, nuts and washers. |
|