3.0Construction:

Marley / Sigma 1000/1200 CoolingTower / Specifications: Base

Specifications

Specification Value

3.0Construction:

16

3.1

The tower shall be capable of with-

The limiting water quality values indicated are those which are

 

standing water having a pH of 6.5 to

acceptable for the normal materials of construction specified. If

 

8.0; a chloride content (NaCl) up to 750

water of more aggressive quality is anticipated please change

 

ppm; a sulfate content (SO4 ) up to

hardware material requirement to 300 Series stainless steel, as

 

1200 ppm; a sodium bicarbonate con-

indicated below and following.

 

tent (NaHCO3) up to 200 ppm; a cal-

 

 

cium content (CaCO3) up to 800 ppm;

 

 

silica (SiO2) up to 150 ppm; and design

 

 

hot water temperatures up to 120°F.

 

 

The circulating water will contain no

 

 

oil, grease, fatty acids, or organic sol-

 

 

vents.

 

3.2The structural framework of the tower shall be Douglas Fir, designed in accor- dance with CTI STD-114. Nylon shear plates shall be utilized to transmit loads at critical joints, and all fasteners shall be in accordance with CTI STD-119. Basic design criteria shall be 30 psf wind load and 5%g seismic load.

3.3All wood components shall be treated

 

after fabrication with chromated cop-

Cooling Technology Institute standards take into account the hot,

 

per arsenate (CCA) by the full-cell

humid environment in which a cooling tower normally operates.

 

process to a chemical retention of 0.4

This environment can render the limits of customary construction

 

lbs/ft3.

standards inadequate for cooling tower design.

3.4

Structural columns and diagonals shall

The importance of shear plates is discussed at length in

 

be 4"x4". Framing girts may be 2"x4",

Marley Difference, “Item S-3”. Ask your Marley representative for

 

except for those supporting the hot

a copy.

 

water basins and fill. Those girts shall

See notes on page 27 regarding the use and availability of red-

 

be 2"x6" minimum, located both sides

 

of the support columns.

wood.

3.5

Multicell towers shall include treated

Specification of minimum member sizes assures that all offerings

 

Douglas Fir plywood partitions

will conform to an industrial level of construction.

 

between cells in the plenum area.

Multicell towers must have plenum partitions between cells.

 

Partitions shall extend the full height of

 

the tower from the base of fill to the

Otherwise, air will be induced downward through an inoperative

 

underneath side of the fan deck.

fan, bypassing the fill entirely. Without these partitions, part-load

 

 

or off-season operation of the tower would be completely unsat-

3.6

Column lines shall be on no greater

isfactory.

 

than 4'-0" longitudinal centers, and

 

 

the base of all perimeter columns

 

 

shall be firmly anchored to galvanized

 

 

steel base plates. Framing joints shall

 

 

be made with 1/2" diameter or larger

 

 

series 300 stainless steel machine

 

 

bolts, nuts and washers.

 