SPX Cooling Technologies 1200 Plan, Tower, Dimensions, Operating Weight lb, Model, Single Cell

Models: 1000 1200

1 32
Download 32 pages 15.22 Kb
Page 10
Image 10
Manual background

Marley / Sigma 1200 CoolingTower / Engineering Data : Support

10

115/8"

 

 

ANCHOR BOLT

 

 

 

 

 

 

L

 

 

C

 

 

 

6'-9 3/8"

ANCHOR BOLT

 

 

L

 

 

C

OVERALL LENGTH OF BASIN

7 1/2"Manual backgroundManual background C BAYS @ 4'-0 = L Manual backgroundManual background 7 1/2"

EACH ADDITIONAL CELL = L

CL ANCHOR BOLT

CL COL.

ANCHOR BOLTCL

AIR INLET FACE

OVERFLOW

BASIN

TOWER

B

ANCHOR BOLT

 

 

WOVERALLWIDTHOF

BASIN

 

 

4"

 

ENDWALLFACE

 

 

ANCHOR BOLT

 

 

L

 

 

L

 

 

 

 

C

 

 

C

 

 

 

 

 

A

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

6'-9 3/8"

 

ANCHOR BOLT

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

C

 

 

115/8"Manual background

SUMP

ADDITIONAL SUMP

WHEN REQUIRED

AIR INLET FACE

ENDWALL FACE

Plan

Tower

 

 

Dimensions

 

 

Operating Weight lb

Model

W

A

B

C

L

Single Cell

Each Cell Add

 

 

 

 

 

 

 

 

1211

31'-10"

8'-6"

7'-10"

4

16'-0"

61250

55900

 

 

 

 

 

 

 

 

1221

33'-10"

9'-6"

8'-10"

4

16'-0"

65530

60660

 

 

 

 

 

 

 

 

1231

33'-10"

9'-6"

8'-10"

5

20'-0"

77960

73110

 

 

 

 

 

 

 

 

1241

33'-10"

9'-6"

8'-10"

6

24'-0"

93790

88940

 

 

 

 

 

 

 

 

1251

37'-10"

11'-6"

10'-10"

6

24'-0"

101020

95740

 

 

 

 

 

 

 

 

1261

37'-10"

11'-6"

10'-10"

7

28'-0"

116260

111000

 

 

 

 

 

 

 

 

NOTE

1Use this bulletin for preliminary layouts only. All dimensions show anchor bolt locations. Obtain current drawings from your Marley sales representative before designing supports.

2Note carefully anchor bolt location relative to beam orientation. See plan above.

3Other contractors or purchaser must design and erect supporting steel.

4If steel beams are used, they must include 78" dia. holes to accept anchor bolts provided. If concrete beams or pilasters are used, 34" dia. anchor bolts embedded in the concrete must be provided by others.

5Maintain no less than 2'-0" of clear space at Endwall Faces for construction purposes. Air Inlet Faces must have unobstructed air supply. Consult your Marley sales representative if nearby obstructions may interfere.

6Operating weight is wet weight of tower and wood basin, including 6" of water in the collection basin. This is the recommended operating water level for all models.

Page 10
Image 10
SPX Cooling Technologies 1200, 1000 Plan, Tower, Dimensions, Operating Weight lb, Model, Single Cell, Each Cell Add