Marley / Sigma 1000/1200 CoolingTower / Specifications: Base
Specifications | Specification Value |
7.0Hot Water Distribution System:
20
7.1 | The mechanical equipment support/ | ■ |
| crossover pipe shall deliver water to | towers. These basins are out where they can be easily inspect- |
| two open hot water basins per cell | |
| at the fan deck elevation. Water shall | systems of counterflow towers, sandwiched between the top of |
| exit these basins to the fill by gravity | the fill and the drift eliminators, are extremely awkward to access |
| through metering | and maintain. |
| pylene nozzles situated in the basin |
|
| floor. Nozzles shall be easily removable | Marley |
| and replaceable. | the tower, and provide a continuing means of |
7.2 | between hot water | |
as well. Towers without valves do not provide this valuable oper- | ||
| control valves shall be provided at | ating flexibility. |
| the inlet to each basin. These valves |
|
| shall permit both flow balancing and |
|
| maintenance |
|
| or portions of cells. Valves shall have |
|
| machined cast iron bodies, with stain- |
|
| less steel operating stems, and heavy- |
|
| duty locking handles. |
|
8.0Casing:
8.1Tower endwalls shall be cased with ribbed FRP panels, lapped and sealed to prevent leakage. Tower corners shall be finished with FRP corner rolls.
9.0Access:
9.1Single cell towers shall include a 33" wide by 61" high molded FRP access door in one endwall casing for access to the interior of the tower. Casing access door shall be hinged and equipped with a latch operable from both inside and outside the tower. Multicell towers shall have an access door in both endwalls, and shall include
| a | ■The access doors on other towers may be unreasonably small. | |
| tion to give free access through the | Specifying the size of the door will cause those bidders to take | |
| tower. |
| exception, alerting you to a potential maintenance headache. |
9.2 | The top of the tower shall be equipped | Good maintenance practice requires periodic access to the top of | |
| with a sturdy 42" high wood guardrail | the tower to inspect the distribution basins, as well as the struc- | |
| system; top rails, intermediate rails, | tural integrity of the fan deck, fan cylinder, and | |
| and toeboards; conforming to OSHA | fan blade securing hardware. And there are no | |
| standards. Posts shall be 4"x4", on no | ing tower designs that are immune to this need! | |
| greater than |
| |
| shall be 2"x4". Single 2"x4" top rail will |
| |
| be acceptable up to |
| |
|
| ||
| shall be included. | ➠ |
|
|
|
|