FLOW TEST PROCEDURE

The correct performance of this procedure will verify if the auxiliary circuit of the carrier is adequate to properly oper- ate a Stanley attachment.

This procedure is generic in form. It is the end users re- sponsibility to ensure that this procedure will work with his specific type of equipment.

If an adequate flow meter is not available contact your Stanley Hydraulic Distributor for assistance.

Test Procedure

1.With the auxiliary circuit (or kit) completely installed connect the flow meter between the tool inlet and outlet hoses.

NOTE: Always use the hoses that are supplied for the attachment and make sure the machine hydraulic oil is between 90° to 120° F. This will assure correct read- ings and adjustments.

2.With the machine setting at the mode that’s going to be used to operate the attachment record the GPM _____.

Locate the correct flow for the attachment in the manual under the specification section. Adjust the machine to the correct GPM.

NOTE: If possible, always set the machine to the high- est GPM output mode. This will prevent the operator from over flowing the attachments.

3.Once the correct GPM flow is achieved fully open the restrictor on the flow meter.

4.With the machine in the attachment mode set in step 2 record the back-pressure. At this point the pressure read- ing on the pressure gauge is the back-pressure in the cir- cuit. This pressure must not exceed 200 psi/13.5 bar.

Excessive back-pressure will slow the attachments opera- tion and lead to premature seal failures and over heating.

Record the back-pressure ______ psi.

5.Close the restrictor valve on the flow meter until the attachment relief starts to crack or open. The relief valve opens when the flow rate (GPM), indicated on the flow meter begins to decline rapidly. Locate the tools operating system relief pressure in the specification section in the manual. Adjust attachment relief to specification.

NOTE: The relief valve pressure must be greater than the operating pressure of the attachment and three times the back-pressure. Never use the relief valve to control the flow rate in the circuit. Cracking pressure means the loss of 4 or more GPM.

Record the relief cracking pressure _____ psi.

Example:

Operation pressure of a breaker is 2700 psi. Back-pres- sure is 150 psi. A good rule to follow when setting the re- lief, multiply the back pressure by 3 then add this number to the operation pressure of the attachment.

Operating Pressure

2700 psi

Back-pressure

450 psi

Operating pressure of the tool

3150 psi

The relief valve setting must be greater than the estimated operating pressure of the tool. If the setting is lower, dam- age to the circuit may occur. Excess heat will be gener- ated in the circuit which will damage the attachment and carrier.

Heat Load Test

With the installation kit properly installed and adjusted per the above procedure, conduct the head load test as fol- lows.

1.Connect the flow meter between the tool inlet and out- let hoses.

2.With the carrier set in the attachment mode, restrict the flow meter until a pressure of 1000 psi is achieved. This pressure must be maintained throughout the heat test.

NOTE: Closing of the restrictor may be required as the temperature increases.

Monitor the oil temperature from the flow meter until no change is noted. Record the time required for oil to stabi- lize. Record the surrounding temperature (ambient tem- perature). Record the time required to stabilize ______

minutes.

Record the stabilized oil temperature ______F.

Record the ambient temperature ______ F.

The “heat rise” is calculated as the stabilized temperature minus the ambient temperature.

HSX User Manual ◄ 11

Page 11
Image 11
Stanley Black & Decker HSX SERIES user manual Flow Test Procedure, Heat Load Test