FLOW TEST PROCEDURES
The correct performance of this procedure will verify if the auxiliary circuit of the carrier is adequate to properly operate a Stanley attachment.
This procedure is generic in form. It is the end users responsibility to ensure that this procedure will work with his specific type of equipment.
If an adequate flow meter is not available contact your Stanley Hydraulic Distributor for assistance.
TEST PROCEDURE
1.With the auxiliary circuit (or kit) completely installed connect the flow meter between the tool inlet and outlet hoses.
NOTE:
Always use the hoses that are supplied for the at- tachment and make sure the machine hydraulic oil is between 90 to 120 °F. This will assure correct readings and adjustments.
2.With the machine setting at the mode that’s going to be used to operate the attachment record the GPM
_____.
Locate the correct flow for the attachment in the manual under the specification section. Adjust the machine to the correct GPM.
NOTE:
If possible, always set the machine to the highest GPM output mode. This will prevent the operator from over flowing the attachments.
3.Once the correct GPM flow is achieved fully open the restrictor on the flow meter.
4.With the machine in the attachment mode set in step 2 record the
Excessive
Record the |
| psi. |
5.Close the restrictor valve on the flow meter until the attachment relief starts to crack or open. The relief valve opens when the flow rate (GPM), indicated on the flow meter begins to decline rapidly. Locate the tools operating system relief pressure in the specifi- cation section in the manual. Adjust attachment re- lief to specification.
NOTE:
The relief valve pressure must be greater than the operating pressure of the attachment and three times the
Record the relief cracking pressure |
| psi. |
Example: |
|
|
Operation pressure of a breaker is 2700 psi.
Operating Pressure | 2700 psi |
450 psi | |
Operating pressure of the tool | 3150 psi |
The relief valve setting must be greater than the estimat- ed operating pressure of the tool. If the setting is lower, damage to the circuit may occur. Excess heat will be generated in the circuit which will damage the attach- ment and carrier.
24 ► MB656 User Manual