INSTALLATION OF VENT SYSTEM, SIDEWALL

With the route of the venting system and selection of materials completed, as discussed in the section of this manual titled PLANNING THE VENT

SYSTEM, the through the wall vent terminal in place and the first section of piping, up to first elbow, installed at the blower it is time to complete the

installation of the venting system for the sidewall installation.

GRADE

SNORKEL

*MIN. 12” (30 cm)

ABOVE GRADE OR

*MIN. 12” (30 cm)

ABOVE

ANTICIPATED

SNOW LEVEL

INSTALL A SNORKEL AS SHOWN

HERE ONLY IF NECESSARY TO

ACHIEVE THE 12” MINIMUM

CLEARANCE ABOVE

THE HIGHEST ANTICIPATED

SNOW LEVEL.

FIGURE 20

It is recommended that the completion of the venting system start at the blower assembly and run to the coupling on the inside wall of the vent terminal, Figure18.

The vent system piping should be supported every 5 feet (1.5 m) of vertical run and every 3 feet (91 cm) of horizontal run. Follow vent pipe manufacturer’s instructions for proper joining procedures.

If necessary to achieve the 12” minimum clearance above the highest anticipated snow level, install a snorkel as shown in bottom portion of Figure 20.

NOTE: With the installation of a snorkel it is necessary to use two 90° elbows that shall be considered along with the

additional vent pipe when calculating maximum equivalent feet of venting.

INSTALLATION OF VERTICAL VENT SYSTEM

A proper flashing or “BOOT” should be used to seal the pipe

where it exits the roof. The total vent system should not exceed the equivalent feet of pipe as listed in Table 1.

Provide support for all pipe protruding through the roof. All piping should be properly secured. The vent system piping should be supported

every 5 feet (1.5 m) of vertical run and every 3 feet (91 cm) of horizontal run. Follow vent pipe manufacturer’s instructions for proper

joining procedures.

FIGURE 21

IMPORTANT

The vent system must terminate so that proper clearances are maintained as cited in local codes or the current edition

of the National Fuel Gas Code (ANSI Z223.1) or the Natural Gas and Propane Installation Code (CAN/CSA-B149.1) and as

listed below:

1.Vent Termination must extend a minimum of 12 inches (30 cm) above roof or 12 inches (30 cm) above the anticipated snow level to prevent blockage of the vent termination, as shown in Figures 20 and 21.

23

Page 23
Image 23
State Industries 197425-004 instruction manual Installation of Vent SYSTEM, Sidewall, Installation of Vertical Vent System

197425-004 specifications

State Industries Model 197425-004 is a noteworthy water heater designed to cater to the needs of both residential and commercial applications. Known for its efficiency and reliability, this model offers a range of features that enhance its appeal to users looking for an effective water heating solution.

One of the primary characteristics of the 197425-004 is its tankless design, which allows for an endless supply of hot water. Unlike traditional water heaters that store hot water in a tank, this model heats water on demand, conserving both energy and space. This is particularly advantageous for households or businesses with fluctuating hot water needs, as it eliminates the risk of running out of hot water during peak usage times.

The technology behind the State Industries 197425-004 incorporates advanced insulation and heat exchange systems, which significantly improve energy efficiency. With a high energy factor rating, this unit minimizes energy consumption, thus reducing utility bills and environmental impact. Users can expect lower operating costs without sacrificing performance, making it a cost-effective option in the long run.

Another defining feature of the 197425-004 is its durable construction. Built with high-quality materials, including corrosion-resistant components, this water heater is designed for longevity. The model also includes a user-friendly digital thermostat, enabling precise temperature control and easy monitoring. This ensures that users can customize their hot water needs according to individual preferences.

In addition to its performance and efficiency, the State Industries 197425-004 prioritizes safety. It is equipped with multiple safety features such as thermal overload protection and precise temperature regulation, reducing the risk of accidents.

Installation is made convenient with this model, as it is compatible with various plumbing systems and does not require complex modifications. Its compact size allows for flexible installation options, whether it is placed indoors or outdoors, depending on user preferences.

In summary, the State Industries 197425-004 represents a perfect blend of cutting-edge technology, energy efficiency, and durability. With its tankless heating system, impressive energy factor, and safety features, it continues to stand out as an excellent choice for reliable hot water solutions in diverse settings.