TPG Power Gas Large Volume Commercial Water Heaters
SPECIFICATIONS
| Nominal | Input |
| Output (Gallons) |
|
|
|
|
|
|
|
|
|
| Ship. |
|
|
| |
Model Number | Storage | Rating |
|
|
|
|
|
|
| Dimensions In Inches |
|
|
| Wt. |
|
| Motor HP | ||
Capacity | BTU/Hr. | First |
| Recovery |
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| w/Burner |
|
| 120V 60 Hz 1 | |||||
| U.S. | Natural | Hour |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| (lbs.) |
|
|
| |||
| Gallons | Gas | Rating | 80°F Rise | 100°F Rise | 140°F Rise | A | B | C | D | E | F | G | H | J |
|
|
| |
|
|
|
|
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TPG 150 140 NEA | 150 | 140,000 | 256 | 170 | 136 | 97 | 831⁄2 | 14 | 1⁄2 | 273⁄4 | 11⁄4 | 361⁄2 | 5 | 47 | 73 | 1292 |
|
|
|
TPG 150 199 NEA | 150 | 199,000 | 313 | 241 | 193 | 138 | 831⁄2 | 14 | 1⁄2 | 273⁄4 | 11⁄4 | 361⁄2 | 6 | 47 | 73 | 1292 | 1⁄7 HP - 2.5 Amps | ||
TPG 150 255 NEA | 150 | 255,000 | 367 | 359 | 247 | 176 | 831⁄2 | 14 | 1⁄2 | 273⁄4 | 11⁄4 | 361⁄2 | 6 | 47 | 73 | 1292 |
|
|
|
TPG 150 270 NEA | 150 | 270,000 | 382 | 327 | 262 | 187 | 831⁄2 | 14 | 1 | 273⁄4 | 11⁄4 | 361⁄2 | 6 | 571⁄2 | 73 | 1397 |
|
|
|
TPG 150 400 NEA | 150 | 400,000 | 507 | 485 | 387 | 277 | 831⁄2 | 14 | 1 | 273⁄4 | 11⁄4 | 361⁄2 | 7 | 571⁄2 | 73 | 1397 | 1⁄4 HP - 4.6 Amps | ||
TPG 150 540 NEA | 150 | 540,000 | 644 | 654 | 524 | 374 | 831⁄2 | 14 | 1 | 273⁄4 | 11⁄4 | 361⁄2 | 8 | 571⁄2 | 73 | 1505 |
|
|
|
TPG 150 720 NEA | 150 | 720,000 | 818 | 873 | 698 | 499 | 831⁄2 | 14 | 11⁄4 | 273⁄4 | 11⁄4 | 361⁄2 | 10 | 571⁄2 | 73 | 1510 | 1⁄3 HP - 5.5 Amps | ||
TPG 200 300 NEA | 200 | 300,000 | 451 | 364 | 291 | 208 | 831⁄2 | 15 | 1 | 321⁄2 | 11⁄2 | 443⁄4 | 6 | 661⁄2 | 73 | 2098 | 1 | ⁄4 | HP - 4.6 Amps |
TPG 200 600 NEA | 200 | 600,000 | 742 | 727 | 582 | 416 | 831⁄2 | 15 | 1 | 321⁄2 | 11⁄2 | 443⁄4 | 8 | 661⁄2 | 73 | 2098 |
| ||
TPG 200 800 NEA | 200 | 800,000 | 936 | 970 | 776 | 554 | 831⁄2 | 15 | 11⁄4 | 321⁄2 | 11⁄2 | 443⁄4 | 10 | 661⁄2 | 73 | 2103 | 1 | ⁄3 | HP - 5.5 Amps |
TPG 200 1000 NEA | 200 | 1,000,000 | 1130 | 1212 | 970 | 693 | 831⁄2 | 15 | 11⁄4 | 321⁄2 | 11⁄2 | 443⁄4 | 10 | 661⁄2 | 73 | 2103 |
| ||
TPG 200 1250 NEA | 200 | 1,250,000 | 1372 | 1515 | 1212 | 866 | 831⁄2 | 15 | 11⁄4 | 321⁄2 | 11⁄2 | 443⁄4 | 12 | 661⁄2 | 73 | 2467 | 1 | ⁄2 | HP - 7.4 Amps |
TPG 200 1500 NEA | 200 | 1,500,000 | 1615 | 1818 | 1455 | 1039 | 831⁄2 | 15 | 11⁄2 | 321⁄2 | 11⁄2 | 443⁄4 | 12 | 811⁄2 | 73 | 2757 |
| ||
TPG 300 300 NEA | 300 | 300,000 | 531 | 364 | 291 | 208 | 911⁄2 | 14 | 1 | 261⁄2 | 11⁄2 | 443⁄4 | 6 | 661⁄2 | 83 | 2150 | 1 | ⁄4 | HP - 4.6 Amps |
TPG 300 600 NEA | 300 | 600,000 | 822 | 727 | 582 | 416 | 911⁄2 | 14 | 1 | 261⁄2 | 11⁄2 | 443⁄4 | 8 | 661⁄2 | 83 | 2150 |
| ||
TPG 300 800 NEA | 300 | 800,000 | 1016 | 970 | 776 | 554 | 911⁄2 | 14 | 11⁄4 | 261⁄2 | 11⁄2 | 443⁄4 | 10 | 661⁄2 | 83 | 2308 | 1 | ⁄3 | HP - 5.5 Amps |
TPG 300 1000 NEA | 300 | 1,000,000 | 1210 | 1212 | 970 | 693 | 911⁄2 | 14 | 11⁄4 | 261⁄2 | 11⁄2 | 443⁄4 | 10 | 661⁄2 | 83 | 2308 |
| ||
TPG 300 1250 NEA | 300 | 1,250,000 | 1452 | 1515 | 1212 | 866 | 911⁄2 | 14 | 11⁄4 | 261⁄2 | 11⁄2 | 443⁄4 | 12 | 661⁄2 | 83 | 2584 | 1 | ⁄2 | HP - 7.4 Amps |
TPG 300 1500 NEA | 300 | 1,500,000 | 1695 | 1818 | 1455 | 1039 | 911⁄2 | 14 | 11⁄2 | 261⁄2 | 11⁄2 | 443⁄4 | 12 | 811⁄2 | 83 | 2774 |
| ||
TPG 400 600 NEA | 400 | 600,000 | 902 | 727 | 582 | 416 | 911⁄2 | 15 | 1 | 321⁄2 | 2 | 55 | 8 | 761⁄2 | 81 | 3207 | 1⁄4 HP - 4.6 Amps | ||
TPG 400 800 NEA | 400 | 800,000 | 1096 | 970 | 776 | 554 | 911⁄2 | 15 | 11⁄4 | 321⁄2 | 2 | 55 | 10 | 761⁄2 | 81 | 3212 |
|
|
|
TPG 400 1000 NEA | 400 | 1,000,000 | 1290 | 1212 | 970 | 693 | 911⁄2 | 15 | 11⁄4 | 321⁄2 | 2 | 55 | 10 | 761⁄2 | 81 | 3212 | 1⁄3 HP - 5.5 Amps | ||
TPG 400 1250 NEA | 400 | 1,250,000 | 1532 | 1515 | 1212 | 866 | 911⁄2 | 15 | 11⁄4 | 321⁄2 | 2 | 55 | 12 | 761⁄2 | 81 | 3212 |
|
|
|
TPG 400 1500 NEA | 400 | 1,500,000 | 1775 | 1816 | 1455 | 1039 | 911⁄2 | 15 | 11⁄2 | 321⁄2 | 2 | 55 | 12 | 911⁄2 | 81 | 3402 |
|
|
|
TPG 400 1750 NEA | 400 | 1,750,000 | 2017 | 2121 | 1697 | 1212 | 911⁄2 | 15 | 2 | 321⁄2 | 2 | 55 | 14 | 911⁄2 | 81 | 3528 | 1⁄2 HP - 7.4 Amps | ||
TPG 400 2000 NEA | 400 | 2,000,000 | 2259 | 2424 | 1939 | 1385 | 991⁄2 | 15 | 2 | 321⁄2 | 2 | 55 | 14 | 911⁄2 | 89 | 3669 |
|
|
|
TPG 500 2250 NEA | 500 | 2,250,000 | 2582 | 2727 | 2182 | 1558 | 110 | 15 | 2 | 321⁄2 | 2 | 55 | 16 | 911⁄2 | 100 | 4277 | 3⁄4 HP - 10.2 Amps | ||
TPG 500 2500 NEA | 500 | 2,500,000 | 2824 | 3030 | 2424 | 1732 | 110 | 15 | 2 | 321⁄2 | 2 | 55 | 16 | 911⁄2 | 100 | 4419 |
|
|
|
TPG 600 720 NEA | 600 | 720,000 | 1178 | 873 | 698 | 499 | 119 | 15 | 11⁄4 | 321⁄2 | 2 | 55 | 10 | 761⁄2 | 109 | 3667 |
|
|
|
TPG 600 1000 NEA | 600 | 1,000,000 | 1450 | 1212 | 970 | 693 | 119 | 15 | 11⁄4 | 321⁄2 | 2 | 55 | 10 | 761⁄2 | 109 | 3667 | 1⁄3 HP - 5.5 Amps | ||
TPG 600 1250 NEA | 600 | 1,250,000 | 1692 | 1515 | 1212 | 866 | 119 | 15 | 11⁄4 | 321⁄2 | 2 | 55 | 12 | 761⁄2 | 109 | 3667 |
|
|
|
TPG 600 1500 NEA | 600 | 1,500,000 | 1935 | 1816 | 1455 | 1039 | 119 | 15 | 11⁄2 | 321⁄2 | 2 | 55 | 12 | 911⁄2 | 109 | 3837 |
|
|
|
TPG 600 1750 NEA | 600 | 1,750,000 | 2177 | 2121 | 1697 | 1212 | 119 | 15 | 2 | 321⁄2 | 2 | 55 | 14 | 911⁄2 | 109 | 3837 | 1⁄2 HP - 7.4 Amps | ||
TPG 600 2000 NEA | 600 | 2,000,000 | 2419 | 2424 | 1939 | 1385 | 119 | 15 | 2 | 321⁄2 | 2 | 55 | 14 | 911⁄2 | 109 | 3837 |
|
|
|
TPG 600 2250 NEA | 600 | 2,250,000 | 2662 | 2727 | 2182 | 1558 | 119 | 15 | 2 | 321⁄2 | 2 | 55 | 16 | 911⁄2 | 109 | 4477 | 3⁄4 HP - 10.2 Amps | ||
TPG 600 2500 NEA | 600 | 2,500,000 | 2904 | 3030 | 2424 | 1732 | 119 | 15 | 2 | 321⁄2 | 2 | 55 | 16 | 911⁄2 | 109 | 4619 |
|
|
|
Certified Minimum Installation Clearances to Combustibles:
Front: 18 inchesASME
Back: 0 inches
Sides: 0 inches
Top: 5 inches
A clearance of 24 inches should be maintained from serviceable parts such as relief valve, power burner, drain valve and anodes (anodes are located on side above cold water inlet).
Minimum gas supply pressure: 7 Inches W.C.
Maximum gas supply pressure: 13 Inches W.C.
TPG models are Category I appliances (Fan Assisted) and require a negative draft. These units should only be commonly vented with other Category I negative draft appliances per the latest addition of the National Fuel Gas Code. An approved/listed Type “B” venting material is recommended. A negative draft of
TPG models are available in both natural gas and propane. To order propane, change the “N” to “P” in the model number. Example: TPG 150 140 PEA
COMMERCIAL 500 Lindahl Parkway, Ashland City, TN 37015 • www.statewaterheaters.com
The Expert’s Choice®