TPX Power Low NOX Large Volume Commercial Water Heaters
SPECIFICATIONS
| Nominal | Input |
| Output (Gallons) |
|
|
|
|
|
|
|
|
|
|
|
| |
Model Number | Storage | Rating |
|
|
|
|
|
|
| Dimensions In Inches |
|
|
|
| Motor HP | ||
Capacity | BTU/Hr. | First |
| Recovery |
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| 120V 60 Hz 1 | |||||
| U.S. | Natural | Hour |
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Gallons | Gas | Rating | 80°F Rise | 100°F Rise | 140°F Rise | A | B | C | D | E | F | G | H | J |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TPX 150 400 NEA | 150 | 400,000 | 507 | 485 | 387 | 277 | 831⁄2 | 14 | 1 | 273⁄4 | 11⁄4 | 54 | 7 | 571⁄2 | 73 | 1 | ⁄7 HP - 2.5 Amps |
TPX 150 540 NEA | 150 | 540,000 | 644 | 654 | 524 | 374 | 831⁄2 | 14 | 1 | 273⁄4 | 11⁄4 | 54 | 8 | 571⁄2 | 73 |
| |
TPX 200 800 NEA | 200 | 800,000 | 936 | 970 | 776 | 554 | 831⁄2 | 15 | 11⁄4 | 321⁄2 | 11⁄2 | 60 | 10 | 72 | 73 |
|
|
TPX 200 1000 NEA | 200 | 1,000,000 | 1130 | 1212 | 970 | 693 | 831⁄2 | 15 | 11⁄4 | 321⁄2 | 11⁄2 | 60 | 10 | 72 | 73 |
|
|
TPX 200 1250 NEA | 200 | 1,250,000 | 1372 | 1515 | 1212 | 866 | 831⁄2 | 15 | 11⁄4 | 321⁄2 | 11⁄2 | 60 | 12 | 72 | 73 |
|
|
TPX 200 1500 NEA | 200 | 1,500,000 | 1615 | 1818 | 1455 | 1039 | 831⁄2 | 15 | 11⁄2 | 321⁄2 | 11⁄2 | 60 | 12 | 72 | 73 |
|
|
TPX 300 800 NEA | 300 | 800,000 | 1016 | 970 | 776 | 554 | 911⁄2 | 14 | 11⁄4 | 261⁄2 | 11⁄2 | 60 | 10 | 72 | 83 |
|
|
TPX 300 1000 NEA | 300 | 1,000,000 | 1210 | 1212 | 970 | 693 | 911⁄2 | 14 | 11⁄4 | 261⁄2 | 11⁄2 | 60 | 10 | 72 | 83 | 1⁄3 HP - 8.6 Amps | |
TPX 300 1250 NEA | 300 | 1,250,000 | 1452 | 1515 | 1212 | 866 | 911⁄2 | 14 | 11⁄4 | 261⁄2 | 11⁄2 | 60 | 12 | 72 | 83 |
|
|
TPX 300 1500 NEA | 300 | 1,500,000 | 1695 | 1818 | 1455 | 1039 | 911⁄2 | 14 | 11⁄2 | 261⁄2 | 11⁄2 | 60 | 12 | 72 | 83 |
|
|
TPX 400 800 NEA | 400 | 800,000 | 1096 | 970 | 776 | 554 | 911⁄2 | 15 | 11⁄4 | 321⁄2 | 2 | 67 | 10 | 84 | 81 |
|
|
TPX 400 1000 NEA | 400 | 1,000,000 | 1290 | 1212 | 970 | 693 | 911⁄2 | 15 | 11⁄4 | 321⁄2 | 2 | 67 | 10 | 84 | 81 |
|
|
TPX 400 1250 NEA | 400 | 1,250,000 | 1532 | 1515 | 1212 | 866 | 911⁄2 | 15 | 11⁄4 | 321⁄2 | 2 | 67 | 12 | 84 | 81 |
|
|
TPX 400 1500 NEA | 400 | 1,500,000 | 1775 | 1816 | 1455 | 1039 | 911⁄2 | 15 | 11⁄2 | 321⁄2 | 2 | 67 | 12 | 84 | 81 |
|
|
TPX 400 1750 NEA | 400 | 1,750,000 | 2017 | 2121 | 1697 | 1212 | 911⁄2 | 15 | 2 | 321⁄2 | 2 | 55 | 14 | 911⁄2 | 81 | 1 HP - 12.4 Amps | |
TPX 400 2000 NEA | 400 | 2,000,000 | 2259 | 2424 | 1939 | 1385 | 991⁄2 | 15 | 2 | 321⁄2 | 2 | 55 | 14 | 911⁄2 | 89 | ||
TPX 600 1000 NEA | 600 | 1,000,000 | 1450 | 1212 | 970 | 693 | 119 | 15 | 11⁄4 | 321⁄2 | 2 | 67 | 10 | 84 | 109 |
|
|
TPX 600 1250 NEA | 600 | 1,250,000 | 1692 | 1515 | 1212 | 866 | 119 | 15 | 11⁄4 | 321⁄2 | 2 | 67 | 12 | 84 | 109 | 1⁄3 HP - 8.6 Amps | |
TPX 600 1500 NEA | 600 | 1,500,000 | 1935 | 1816 | 1455 | 1039 | 119 | 15 | 11⁄2 | 321⁄2 | 2 | 67 | 12 | 84 | 109 |
|
|
TPX 600 1750 NEA | 600 | 1,750,000 | 2177 | 2121 | 1697 | 1212 | 119 | 15 | 2 | 321⁄2 | 2 | 55 | 14 | 911⁄2 | 109 | 1 HP - 12.4 Amps | |
TPX 600 2000 NEA | 600 | 2,000,000 | 2419 | 2424 | 1939 | 1385 | 119 | 15 | 2 | 321⁄2 | 2 | 55 | 14 | 911⁄2 | 109 |
Certified Minimum Installation Clearances to Combustibles: Front: 18 inches
Back: 0 inches
Sides: 0 inches
Top: 5 inches
A clearance of 24 inches should be maintained from serviceable parts such as relief valve, power burner, drain valve and anodes (anodes are located on side above cold water inlet).
Minimum gas supply pressure: 7 Inches W.C.
Maximum gas supply pressure: 13 Inches W.C.
TPX models are Category I appliances (Fan Assisted) and require a negative draft. These units should only be commonly vented with other Category I negative draft appliances per the latest addition of the National Fuel Gas Code. An approved/listed Type “B” venting material is recommended. A negative draft of
ASME
COMMERCIAL 500 Lindahl Parkway, Ashland City, TN 37015 • www.statewaterheaters.com
The Expert’s Choice®